
uREG User Manual
79
4S Ecz+ Zone 3
or
for the direction of energy sourced from
busbars (Ecz–), no backward state.
4T Ecz– Zone 0
4U Ecz– Zone 1
4W Ecz– Zone 2
4X Ecz– Zone 3
Stored active energy sourced from busbars in time
zones.
Range:
0 – 10 000 [MWh]
4Y Ebr+ Zone 0
4Z Ebr+ Zone 1
4a Ebr+ Zone 2
4b Ebr+ Zone 3
Stored reactive energy fed to busbars in time
zones.
Range:
0 – 10 000 [Mvarh]
Energy metered for a period of the time
zone (successive days) for energy fed to
busbars (Ebr+)
or
for the direction of energy sourced from
busbars (Ebr–), no backward state.
4c Ebr– Zone 0
4d Ebr– Zone 1
4e Ebr– Zone 2
4f Ebr– Zone 3
Stored reactive energy from busbars in time
zones.
Range:
0 – 10 000 [Mvarh]
4g Ecz+ total
Total active energy fed to busbars
Range:
0 – 100 000 [MWh]
Energy stored for the entire measurement
period for the energy rate fed to busbars (Ecz+)
or
for energy sourced from busbars (Ecz–), no
return cycles.
4h Ecz– total
Total active energy from busbars.
Range:
0 – 100 000 [MWh]
4i Ebr+ total
Total reactive energy fed to busbars.
Range:
0 – 100 000 [Mvarh]
Energy stored for the entire measurement
period for the energy rate fed to busbars (Ebz+)
or
for energy sourced from busbars (EBr–), no
return cycles.
4j Ebr– total
Total
active
energy
from
busbars.
Range:
0 – 100 000 [Mvarh]
4k tg(Fi) Q3/P3
Tangent of instantaneous phase angle for transformer
load (with sign), calculated as the ratio of 1-second
average 3-phase active and reactive power values.
Range:
0 – 1000
The maximum tangent modulus is
limited to 999.99.
4l tg (Fi) Q3m/P3m
Tangent of the phase angle for transformer load (with
sign), calculated as the ratio of 15-minute peak power
values in the current time zone.
Range:
0 – 1000
4m tg (Fi) zones
Average tangent of phase angle for transformer load
(signed), calculated as the ratio of values of energy
stored in the current time zone: reactive (Ebr+ in zone n)
and active (Ecz+ in zone n) fed to busbars.
Range:
0 – 1000
4n tg (Fi) total average
Average tangent of phase angle for transformer load
(signed), calculated as the ratio of total energy values:
reactive (Ebr+) and active (Ecz+) fed to busbars.
Range:
0 – 1000
4o Σ I1 shutdowns
4p Σ I2 shutdowns
4q Σ I3 shutdowns
4r Σ I4 shutdowns
Cumulated sum of RMS currents shut down by the
master switch.
Range:
Σ I1:
0 – Igr1*thetaIf
[kA]
Σ
I2:
Igr1*thetaIf – Igr2*thetaIf
[kA]
Σ
I3:
Igr2*thetaIf – Igr3*thetaIf
[kA]
Σ
I4:
Igr3*thetaIf – 192*thetaIf
[kA]
, where:
Igr1 – Igr3:
circuit-breaker limit currents;
thetaIf:
transmission ratio of phase current
transformers;
For the purpose of turn-off currents, the
maximum value of current RMS values in L1, L2
and L3 (after a turn-off impulse is sent to the
circuit-breaker coil to the moment of power cut)
is used. The cumulated sum means current
values converted by means of the transmission
ratio into the grid primary side.
The value will be stored regardless of duration
of auxiliary supply interruption.
4s Resistor current
Resistor current
[kA]
4t Voltage U0 2
Voltage U0 in section 2 [VT-2]
4u Voltage U12 2
Line-to-line voltage U12 in section 2 [VT-2]
4v Voltage U23 2
Line-to-line voltage U23 in section 2 [VT-2]
4w Voltage U31 2
Line-to-line voltage U31 in section 2 [VT-2]
Summary of Contents for uREG
Page 2: ...uREG User Manual 2 LogCZIP and uREG are registered trademarks of REGULUS Zygmunt Liszy ski...
Page 4: ...uREG User Manual 4...
Page 8: ...uREG User Manual 8 21 GUIDELINES FOR THE PURCHASER 107 22 WARRANTY 107...
Page 21: ...uREG User Manual 21 Drilling diagram for 10 slot enclosure installation...
Page 22: ...uREG User Manual 22 Drilling diagram for 14 slot enclosure installation...