uREG User Manual
93
16.1.4.
PN-485 INTERFACE (PANEL)
As already mentioned, the operator panel in
u
REG
can be operated remotely → connected
to the central unit by a cable with a length up to 15 m.
Communication involves a separated
RS-485
interface which is symmetrically reproduced on
three side of the IF-x module (installation options → see
7 Modules
and
8 Panel
).
PN-485 interface lines are arranged in a
9-wireDB9F
connector (female) as follows:
+12V
pin 1
- panel supply,
GND
pin 5
- ground,
-12V
pin 6
- panel supply,
Internal pin 4
- for internal use,,
+3.3 V
pin 9
- panel supply
A
pin 8
- Data Input (+),
B
pin 7
- Data Input (–),
Y
pin 2
- Data Output (+),
Z
pin 3
- Data Output (–).
Transmission parameters and the data interchange protocol are specified by firmware and are
not to be tampered with by the user.
Communication with the panel can be disabled using the administrator’s setting
Disable panel
in
Auxiliary settings
(via
Monitor3
). Then, the device able to work without the panel (panel
presence in the system will not be checked or reported).
CAUTION:
Each change in the setting must be applied by momentary disconnection and reconnection of
auxiliary power.
Summary of Contents for uREG
Page 2: ...uREG User Manual 2 LogCZIP and uREG are registered trademarks of REGULUS Zygmunt Liszy ski...
Page 4: ...uREG User Manual 4...
Page 8: ...uREG User Manual 8 21 GUIDELINES FOR THE PURCHASER 107 22 WARRANTY 107...
Page 21: ...uREG User Manual 21 Drilling diagram for 10 slot enclosure installation...
Page 22: ...uREG User Manual 22 Drilling diagram for 14 slot enclosure installation...