uREG User Manual
34
7.7.
VT-2 / VT-1 MODULE (SLOT 2)
The
VT-2
module with double
v
oltage
t
ransformers is mainly designed for supporting ATS
automatic units and wind plants.
The
VT-2
module houses 2 sets of 4 measuring transformers for voltages U0, U1, U2, U3 and 1
current transformer for I0.
Terminals of the
VT-2
module are grouped into 3 x Phoenix-Contact/Wieland slots:
8-pin MSTBA2.5/8-G strip (pitch: 5.00 mm, max 12 A, 250 V) for measurement of
U0, U1, U2, U3
voltages in section 1 within the range (Un: 100 V)
= 0 ÷ 130V;
8-pin MSTBA2.5/8-G strip (pitch: 5.00 mm, max 12 A, 250 V) for measurement of
U0, U1, U2, U3
voltages in section 2 within the range (Un: 100 V)
= 0 ÷ 130V;
2-pin GMSTBA2.5/2-G strip (pitch: 7.50 mm, max 12 A, 400 V) for measurement of
current
I0
within the range (In: 1 A)
= 0 ÷ 10 A.
Fig. 7.7. Terminals of the VT-2 module.
The
VT-2
module (combined with
CT-0
) is required for fulfillment of the following protective
criteria and functions, e.g.:
Overvoltage U> [in Section 1 and 2]
• Power directional
Tripped overvoltage U>T [in Section 1 and 2]
• Internal fSPZ/SCO
Overvoltage U0> [in Section 1 and 2]
• Overcurrent earth-fault criterion I0>
Undervoltage U< [in Section 1 and 2]
• Susceptance B0kier.>
Undervoltage U<T [in Section 1 and 2]
• Conductance G0>
Difference of sectional voltages [1-2]
• Conductance G0>kier.
Frequency [in Section 1 and 2]
• Admittance Y0>
Frequency derivative df/dt>
• Admittance YY0>
Vector Shift
• Underpower for 3-phase reactive power (1 min.) Q3f<
Voltage derivative dU/dt
• Overpower for 3-phase reactive power (1 min.) Q3f>
Second harmonic f100Hz>
• Underpower for 3-phase active power (1 min.) P3f<
BKR capacitor bank control
• Overpower for 3-phase active power (1 min.) P3f>
AWSCz automatic unit controller
• Resistor controller
Synchro-check on both sections
deltaf< [Section 1-2]
The
VT-1
module is identical in terms of functionality, but it features increased measurement
threshold for voltages
U0, U1, U2, U3
within the range
5 – 260 V (optionally 500 V AC)
.
Summary of Contents for uREG
Page 2: ...uREG User Manual 2 LogCZIP and uREG are registered trademarks of REGULUS Zygmunt Liszy ski...
Page 4: ...uREG User Manual 4...
Page 8: ...uREG User Manual 8 21 GUIDELINES FOR THE PURCHASER 107 22 WARRANTY 107...
Page 21: ...uREG User Manual 21 Drilling diagram for 10 slot enclosure installation...
Page 22: ...uREG User Manual 22 Drilling diagram for 14 slot enclosure installation...