uREG User Manual
36
7.9.
VT-6 MODULE (SLOT #2)
VT-6
– voltage transformers module, transformers of the second current s Ig, I0.
Under development.
7.10.
VT-7 MODULE (SLOT #2)
The module has three voltage transformers for
U1, U2, U3
within the range
5 ÷ 260 V
(optionally 500 V AC)
and
two full If stars.
Terminals on the
VT-7
module are grouped into 3 x Wieland slots:
6-pin MSTBA2.5/6-G strip (pitch: 5.00 mm, max 12 A, 250 V)
for measurement of
U1, U2, U3
voltages in section 1 within the range (Un: 230 V)
= 0 ÷ 500 V;
6-pin GMSTBA2.5/6-G strip (pitch: 5.00 mm, max 12 A, 400 V)
for measurement of current
If in section 2
within the range (In: 1 A) = 0 ÷ 10 A.
6-pin GMSTBA2.5/6-G strip (pitch: 5.00 mm, max 12 A, 400 V)
for measurement of current
If in section 3
within the range (In: 1 A)
= 0 ÷ 10 A.
Fig. 7.10. Terminals of the VT-7 module.