Chapter 3: Installation and Configuration
33
3. Plug the power cord into the outlet, and press the clip toward the
power cord until it holds the cord firmly. The clip's central area holding
the plug should face downwards toward the ground, like an inverted
"U". This allows gravity to keep the clip in place.
4. Repeat the same steps to install clips and power cords on the other
outlets.
Tip: Raritan also provides other mechanisms to securely hold the power
cords in place. See
Locking Outlets and Cords
(on page 411).
Connecting Environmental Sensors (Optional)
To enable the detection of environmental factors around the Dominion PX,
connect one or more Raritan environmental sensors to the Dominion PX
device.
The maximum distance for all sensor cabling plugged into the product's
sensor port should not exceed 30 meters/100 feet. Contact Raritan
Technical Support if you have questions.
You can connect up to 16 environmental sensors to a Dominion PX device
by using a Raritan sensor hub.
Note that a Raritan environmental sensor usually contains more than one
sensor. For example, a DPX-T2H2 counts as 4 sensors, and a DPX-T3H1
counts as 4 sensors.
Warning: For proper operation, wait for 15~30 seconds between each
connection operation or each disconnection operation of environmental
sensors.
To directly connect one or multiple environmental sensors:
Plug the connector of the environmental sensor into the SENSOR port
on your Dominion PX device.
Note: Depending on the model you purchased, the total number of
SENSOR ports varies.