Chapter 7: Using the Command Line Interface
241
Inlet Sensor Threshold Information
This command syntax shows the specified inlet sensor's threshold-related
information.
#
show sensor inlet <n> <sensor type>
To show detailed information, add the parameter "details" to the end of the
command.
#
show sensor inlet <n> <sensor type>
details
Variables:
<n> is the number of the inlet whose sensors you want to query.
<sensor type> is one of the following sensor types:
Sensor type
Description
current Current
sensor
voltage Voltage
sensor
activePower Active
power
sensor
apparentPower
Apparent power sensor
powerFactor
Power factor sensor
activeEnergy
Active energy sensor
unbalancedCurrent
Unbalanced load sensor
Displayed information:
Without the parameter "details," only the reading, state, threshold,
deassertion hysteresis and assertion delay settings of the specified
inlet sensor are displayed.
With the parameter "details," more sensor information is displayed,
including accuracy and range.
If the requested sensor type is not supported, the message "Not
available" is displayed.