Chapter 3: Installation and Configuration
16
Preparing the Installation Site
1. Make sure the installation area is clean and free of extreme
temperatures and humidity.
Note: If necessary, contact Raritan Technical Support for the
maximum operating temperature for your model. See
Maximum
Ambient Operating Temperature
(on page 387).
2. Allow sufficient space around the Dominion PX device for cabling and
outlet connections.
3. Review
the
Safety Instructions
(on page iii) listed in the beginning of
this user guide.
Filling Out the Equipment Setup Worksheet
An Equipment Setup Worksheet is provided in this guide. See
Equipment
Setup Worksheet
(on page 389). Use this worksheet to record the model,
serial number, and use of each IT device connected to the PDU.
As you add and remove devices, keep the worksheet up-to-date.
Checking the Branch Circuit Rating
This section describes the rating of the branch circuit supplying power to
the PDU:
The rating of the branch circuit shall be in accordance with national
and local electrical codes.
For North American, the rating of the branch circuit may be up to
125% greater than the rating of the PDU, unless prohibited by
national or local electrical codes.
20A for PDUs rated at 16A input current
30A for PDUs rated at 24A input current
40A for PDUs rated at 32A input current
50A for PDUs rated at 35A input current
50A for PDUs rated at 40A input current
60A for PDUs rated at 45A input current
In North America, external overcurrent protectors shall be certified
by UL/CSA (or equivalent certification). In other regions or
countries, make sure they comply with national and local electrical
codes.