Chapter 7: Using the Command Line Interface
331
Example
The following command sets the Lower Warning threshold for the pole 3
(L3-L1) voltage of the inlet 1 to 190V. It also enables the lower warning
threshold if this threshold has not been enabled yet.
config:#
sensor inletpole 1 L3 voltage lowerWarning 190
Setting the Inlet Pole's Deassertion Hysteresis
This command syntax configures the deassertion hysteresis value of an
inlet pole.
config:#
sensor inletpole <n> <p> <sensor type> hysteresis <value>
Variables:
<n> is the number of the inlet whose pole sensors you want to
configure.
<p> is the label of the inlet pole that you want to configure.
Pole
Label
<p>
Current sensor
Voltage sensor
1
L1
L1
L1 - L2
2
L2
L2
L2 - L3
3
L3
L3
L3 - L1
<sensor type> is one of the following sensor types:
Sensor type
Description
current Current
sensor
voltage Voltage
sensor
activePower Active
power
sensor
apparentPower
Apparent power sensor
powerFactor
Power factor sensor
activeEnergy
Active energy sensor
unbalancedCurrent
Unbalanced load sensor
Note: If the requested sensor type is not supported, the message "Not
available" is displayed.