E-21
Technical Specifications
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames E & F
Electrical Ratings (Induction): 890SD Frame F, 400V
Power Supply = 380-460V ±10%, 50/60Hz
±
5%
Motor power, output current and input current must not be exceeded under steady state operating conditions. Input
currents listed at 400Vac 50Hz for kW ratings and 460Vac 60Hz for Hp ratings.
Model Number
(Europe)
Catalog Number
(North America)
Motor
Power
Output
Current
(A)
(note 1)
AC Input
Current
(A)
Heatsink
Power
Loss (W)
Total
Power
Loss
(W)
Maximum
Switching
Frequency
(kHz)
Input
Bridge I
2
t
(A
2
s)
FRAME F :
Prospective short circuit current 18kA.
Constant Torque
Output Overload Motoring 150% overload for 60 seconds (all vector modes) 180% for 1s (V/Hz mode)
890SD-433105F...
55kW
105
114
920
1220
3
100,000
890SD/4/0105F/.. 75Hp
100
99
900
1130
3
100,000
890SD-433145F...
75kW
145
143
1320
1670
3
100,000
890SD/4/0145F/.. 100Hp 130
124
1200
1500
3
100,000
890SD-433145F...
90kW
180
164
1490
1950
3
100,000
890SD/4/0156F/.. 125Hp 156
148
1340
1780
3
100,000
890SD-433180F...
110kW 180
164
1490
1950
3
100,000
890SD/4/0180F/.. 150Hp 180
169
1670
2180
3
100,000