E-17
Technical Specifications
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames E & F
Electrical Ratings (Induction): 890CD Frame E, 500V
Power Supply = 380-500V ±10%, 50/60Hz
±
5%
Motor power, output current and input current must not be exceeded under steady state operating conditions.
Input currents listed at 705V DC (from 500Vac 50Hz) for kW ratings, assuming a 3% line choke is fitted to the
890CS unit.
500V unit full power ratings are only available at 500V. The unit can be operated between 380-500V supply
voltage with reduced output power below 500V.
Model Number
(Europe)
Catalog Number
(North America)
Motor
Power
Output
Current
(A)
(note 1)
DC Input
Current
rms
(A)
Heatsink
Power Loss
(W)
Total
Power Loss
(W)
Maximum
Switching
Frequency
(kHz)
FRAME E :
Prospective short circuit current 65kA.
Constant Torque
Output Overload Motoring 150% overload for 60 seconds (all vector modes) 180% for 1s (V/Hz mode)
890CD-532730E..
37kW
67
66
615
727
3, 6
-
890CD-532870E...
45kW
79
80
722
848
3, 6
-
Quadratic Torque
Output Overload Motoring 110% for 60s (V/Hz mode)
890CD-532730E...
45kW
79
82
532
660
3
-
890CD-532870E...
55kW
98
98
627
775
3
-
Note 1:
Up to the highest supply voltage that maintains shaft power less than the product power rating, for a typical
induction motor. Derated for operation above this supply voltage.