Programming
D-109
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames E & F
PHASE TUNING
SETUP::PHASE CONTROL::PHASE TUNING
The Tuning function block provides a means of injecting a speed offset or a phase offset in a selected wave form to assist the
tuning of the speed and phase loops. It would be unusual for both tests to be active together.
Parameter Descriptions
ENABLE PHASE
PREF: 111.04
Default: FALSE
Range: FALSE / TRUE
Activates a test function to add a test signal to the position demand (phase offset).
ENABLE SPEED
PREF: 111.02
Default: FALSE
Range: FALSE / TRUE
Activates a test function to add a test signal to the speed demand (speed offset).
REFERENCE TYPE
PREF: 111.08
Default: 0
Range: See below
Type of tuning reference, either square, sine, or triangular wave.
Enumerated Value
:
Type
0 : SQUARE
1 : SINUSOIDAL
2 : TRIANGULAR
SPEED AMPLITUDE
PREF: 111.09
Default: 0.1000 rev/s
Range: 0.0000 to 100.0000
rev/s
This parameter sets the amplitude of the test signal. The signal is symmetric. (i.e. for an amplitude of 1 % the test signal varies
by +/- 1.0 %). In speed test mode, the unit of this parameter are load speed, in position test mode, the unit is percent of 1 load
revolution.
POSN AMPLITUDE
PREF: 111.16
Default: 1.0000 deg
Range: 0.0000 to 100.0000 deg
This parameter sets the amplitude of the test signal. The signal is symmetric. (i.e. for an amplitude of 1 % the test signal varies
by +/- 1.0 %). In speed test mode, the unit of this parameter are load speed, in position test mode, the unit is percent of 1 load
revolution.