
E-15
Technical Specifications
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames E & F
Electrical Ratings (Induction): 890CD Frame F, 400V
Power Supply = 380-460V ±10%, 50/60Hz
±
5%
Motor power, output current and input current must not be exceeded under steady state operating conditions.
Input currents listed at 560V DC (from 400Vac 50Hz) for kW ratings and 650V DC (from 460Vac 60Hz) for Hp
ratings, assuming a 3% line choke is fitted to the 890CS unit.
Model Number
(Europe)
Catalog Number
(North America)
Motor
Power
Output
Current
(A)
(note 1)
DC Input
Current
rms
(A)
Heatsink
Power Loss
(W)
Total
Power Loss
(W)
Maximum
Switching
Frequency
(kHz)
FRAME F :
Prospective short circuit current 65kA.
Constant Torque
Output Overload Motoring 150% overload for 60 seconds (all vector modes) 180% for 1s (V/Hz mode)
890CD-433105F..
55kW
105
123
665
965
3
890CD/4/0105F/..
75Hp
100
107
645
875
3
890CD-433145F..
75kW
145
166
992
1342
3
890CD/4/0145F/..
100Hp
130
144
872
1172
3
890CD-433156F..
90kW
180
203
1190
1650
3
890CD/4/0156F/..
125Hp
156
176
1040
1480
3
890CD-433180F..
90kW
180
203
1190
1650
3
890CD/4/0180F/..
150Hp
180
213
1370
1880
3