5-23
Set Values
Value
Function
Description
0
Fault output
ON: Fault output (with protective function working)
1
Operation in progress
ON: Operation in progress (with RUN command input or
inverter output)
2
Frequency detection
ON: Frequency detection (with frequency reference
coinciding with output frequency)
3
Idling
ON: Idling (at less than min. output frequency)
4
Frequency detection 1 ON: Output frequency
y
frequency detection level (n58)
5
Frequency detection 2 ON: Output frequency
x
frequency detection level (n58)
6
Overtorque being
monitored
(NO-contact output)
Output if any of the following parameter conditions is
satisfied.
•
Overtorque detection function selection (n59)
•
Overtorque detection level (n60)
7
Overtorque being
monitored
(NC-contact output)
•
Overtorque detection level (n60)
•
Overtorque detection time (n61)
Note NO contact: ON with overtorque being detected;
NC contact: OFF with overtorque being detected
10
Alarm output
ON: Alarm being detected (Nonfatal error being
detected)
11
Base block in
progress
ON: Base block in progress (in operation with output
shutoff)
12
RUN mode
ON: Local mode (with the Digital Operator)
13
Inverter ready
ON: Inverter ready to operate (with no fault detected)
14
Fault retry
ON: Fault retry (Inverter resetting with fault retry (n48)
not set to 0)
15
UV in progress
ON: Undervoltage being monitored (main circuit
undervoltage UV1 detected)
16
Rotating in reverse
direction
ON: Rotating in reverse direction
17
Speed search in
progress
ON: Speed search in progress
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3JV-AB001
Page 1: ...USER S MANUAL FIRST DRAFT SYSDRIVE 3G3JV Compact Simplified Inverter Cat No I528 E1 1...
Page 3: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Page 9: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 43: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Page 52: ...3 10 Preparing for Operation and Monitoring Chapter 3...
Page 53: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 62: ...4 10 Test Run Chapter 4...
Page 131: ...7 22 Maintenance Operations Chapter 7...
Page 132: ...Chapter 8 Specifications 8 1 Inverter Specifications 8 2 Option Specifications 8...
Page 138: ...Chapter 9 List of Parameters 9...
Page 150: ...Chapter 10 Using the Inverter for a Motor 10...
Page 165: ...Revision History 10 2...
Page 166: ...Cat No I528 E1 1 SYSDRIVE 3G3JV Compact Simplified Inverter USER S MANUAL...