5-2
This section explains the basic settings required to operate and stop the
Inverter.
The settings of parameters described here will be sufficient for simple In-
verter operations.
First, make these basic settings, then skip to the explanations of those spe-
cial functions, even when your application requires special functions, such
as stall prevention, carrier frequency setting, overtorque detection, torque
compensation, slip compensation. Refer to
tion.
5-1
Initial Settings
•
The following initial settings are required.
Parameter Write-prohibit Selection/Parameter Initialization (n01): Set n01 to 1 so
that n01 through n79 can be set or displayed.
Rated Motor Current (n32): Check the rated current on the motor nameplate and set
the parameter.
H
Setting the Parameter Write-prohibit Selection/Parameter
Initialization (n01)
•
Set n01 to 1 so that n01 through n79 can be set or displayed.
n01
Parameter Write-prohibit Selection/Parameter
Initialization
Changes during
operation
No
Setting
range
0, 1, 6, 8, 9
Unit of
setting
1
Default setting
1
Note This parameter makes it possible to write-prohibit parameters, change the pa-
rameter set or displayed range, or initialize all parameters to default values.
Set Values
Value
Description
0
Only n01 can be displayed and set. The n02 through n79 parameters can be
displayed only.
1
The n01 through n79 parameters can be displayed and set.
6
Only the error log memory is cleared.
8
Enables the initialization of all parameters in 2-wire sequence so that the
parameters will return to default values.
9
Enables the initialization of all parameters in 3-wire sequence.
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3JV-AB001
Page 1: ...USER S MANUAL FIRST DRAFT SYSDRIVE 3G3JV Compact Simplified Inverter Cat No I528 E1 1...
Page 3: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Page 9: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 43: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Page 52: ...3 10 Preparing for Operation and Monitoring Chapter 3...
Page 53: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 62: ...4 10 Test Run Chapter 4...
Page 131: ...7 22 Maintenance Operations Chapter 7...
Page 132: ...Chapter 8 Specifications 8 1 Inverter Specifications 8 2 Option Specifications 8...
Page 138: ...Chapter 9 List of Parameters 9...
Page 150: ...Chapter 10 Using the Inverter for a Motor 10...
Page 165: ...Revision History 10 2...
Page 166: ...Cat No I528 E1 1 SYSDRIVE 3G3JV Compact Simplified Inverter USER S MANUAL...