5-3
H
Setting the Rated Motor Current (n32)
Set the rated motor current (n32) in order to prevent the motor from burning due to over-
loading.
Check the rated current on the motor nameplate and set the parameter.
This parameter is used for the electronic thermal function for motor overload detection
(OL1). By setting the correct parameter, the overloaded motor will be protected from
burning.
n32
Rated Motor Current
Changes during
operation
No
Setting
range
0.0% to 120% (A) of rated
output current of Inverter
Unit of
setting
0.1 A
Default setting
(see
note 1)
Note 1. The standard rated current of the maximum applicable motor is the default
rated motor current.
Note 2. Motor overload detection (OL1) is disabled by setting the parameter to 0.0.
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3JV-AB001
Page 1: ...USER S MANUAL FIRST DRAFT SYSDRIVE 3G3JV Compact Simplified Inverter Cat No I528 E1 1...
Page 3: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Page 9: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 43: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Page 52: ...3 10 Preparing for Operation and Monitoring Chapter 3...
Page 53: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 62: ...4 10 Test Run Chapter 4...
Page 131: ...7 22 Maintenance Operations Chapter 7...
Page 132: ...Chapter 8 Specifications 8 1 Inverter Specifications 8 2 Option Specifications 8...
Page 138: ...Chapter 9 List of Parameters 9...
Page 150: ...Chapter 10 Using the Inverter for a Motor 10...
Page 165: ...Revision History 10 2...
Page 166: ...Cat No I528 E1 1 SYSDRIVE 3G3JV Compact Simplified Inverter USER S MANUAL...