9-7
Pa-
ram-
eter
No.
Ref-
er-
ence
page
Changes
during
opera-
tion
Default
setting
Unit
of set-
ting
Set-
ting
range
Description
Name
n39
Multi-func-
tion input 4
(Input termi-
nal S5)
12
External
base block
command
(NO)
ON: Output shut off (while
motor coasting to a stop
and “bb” flashing)
2 to 8,
10 to
22, 34
1
6
No
nal S5)
13
External
base block
command
(NC)
OFF: Output shut off (with
motor free running and “bb”
flashing)
14
Search com-
mand
(Searching
starts from
maximum
frequency)
ON: Speed search
(Searching starts from n09)
15
Search com-
mand
(Searching
starts from
preset fre-
quency)
ON: Speed search
16
Acceleration/
Decelera-
tion-prohibit
command
ON: Acceleration/Decelera-
tion is on hold (running at
parameter frequency)
17
Local or re-
mote selec-
tion
ON: Local mode (operated
with the Digital Operator)
19
Emergency
stop fault
(NO)
The Inverter stops accord-
ing to the setting in n04 for
interruption mode selection
with the emergency stop in-
put turned ON
20
Emergency
stop alarm
(NO)
e e e ge cy s p
put turned ON.
NO: Emergency stop with
the contact closed.
NC: Emergency stop with
the contact opened
21
Emergency
stop fault
(NC)
NC: Emergency stop with
the contact opened.
Fault: Fault output is ON
and reset with RESET
input. Alarm output is ON
(
t
i d)
22
Emergency
stop alarm
(NC)
input. Alarm output is ON
(no reset required).
“STP” is displayed (lit with
fault input ON and flashes
with alarm input ON)
34
Up or down
command
Up or down command (set
in n39 only)
By setting n39 to 34, the
set value in n38 is ignored
and the following setting
are forcibly made.
S4: Up command
S5: Down command
List of Parameters
Chapter 9
Summary of Contents for SYSDRIVE 3G3JV-AB001
Page 1: ...USER S MANUAL FIRST DRAFT SYSDRIVE 3G3JV Compact Simplified Inverter Cat No I528 E1 1...
Page 3: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Page 9: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 43: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Page 52: ...3 10 Preparing for Operation and Monitoring Chapter 3...
Page 53: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 62: ...4 10 Test Run Chapter 4...
Page 131: ...7 22 Maintenance Operations Chapter 7...
Page 132: ...Chapter 8 Specifications 8 1 Inverter Specifications 8 2 Option Specifications 8...
Page 138: ...Chapter 9 List of Parameters 9...
Page 150: ...Chapter 10 Using the Inverter for a Motor 10...
Page 165: ...Revision History 10 2...
Page 166: ...Cat No I528 E1 1 SYSDRIVE 3G3JV Compact Simplified Inverter USER S MANUAL...