6-4
n75
Low Carrier Frequency at Low Speed
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
Low carrier frequency at low speed disabled.
1
Low carrier frequency at low speed enabled.
•
Normally set n75 to 0.
•
When the output frequency is 5 Hz or higher and the output current rate is 110% or less,
the carrier frequency will be automatically reduced to 2.5 kHz with n75 set to 1. If the
load is heavy at low speed, the Inverter will withstand higher overcurrent by suppres-
sing the heat radiation of the Inverter caused by the carrier frequency.
•
This function is enabled with 2, 3, or 4 set in n46 for carrier frequency.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3JV-AB001
Page 1: ...USER S MANUAL FIRST DRAFT SYSDRIVE 3G3JV Compact Simplified Inverter Cat No I528 E1 1...
Page 3: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Page 9: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 43: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Page 52: ...3 10 Preparing for Operation and Monitoring Chapter 3...
Page 53: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 62: ...4 10 Test Run Chapter 4...
Page 131: ...7 22 Maintenance Operations Chapter 7...
Page 132: ...Chapter 8 Specifications 8 1 Inverter Specifications 8 2 Option Specifications 8...
Page 138: ...Chapter 9 List of Parameters 9...
Page 150: ...Chapter 10 Using the Inverter for a Motor 10...
Page 165: ...Revision History 10 2...
Page 166: ...Cat No I528 E1 1 SYSDRIVE 3G3JV Compact Simplified Inverter USER S MANUAL...