2-22
H
Wiring on the Output Side of the Main Circuit
D
Connecting the Terminal Block to the Load
Connect output terminals U/T1, V/T2, and W/T3 to motor lead wires U, V, and W.
Check that the motor rotates forward with the forward command. Switch over any two of
the output terminals to each other and reconnect if the motor rotates in reverse with the
forward command.
D
Never Connect a Power Supply to Output Terminals
Never connect a power supply to output terminals U/T1, V/T2, or W/T3.
If voltage is applied to the output terminals, the internal circuit of the Inverter will be dam-
aged.
D
Never Short or Ground Output Terminals
If the output terminals are touched with bare hands or the output wires come into contact
with the Inverter casing, an electric shock or grounding will occur. This is extremely haz-
ardous.
Also, be careful not to short the output wires.
D
Do not Use a Phase Advancing Capacitor or Noise Filter
Never connect a phase advance capacitor or LC/RC Noise Filter to the output circuit.
Doing so will result in damage to the Inverter or cause other parts to burn.
D
Do not Use an Electromagnetic Switch of Magnetic Contactor
Do not connect an electromagnetic switch of magnetic contactor to the output circuit.
If a load is connected to the Inverter during running, an inrush current will actuate the
overcurrent protective circuit in the Inverter.
D
Installing a Thermal Relay
The Inverter has an electronic thermal protection function to protect the motor from
overheating. If, however, more than one motor is operated with one inverter or a multi-
polar motor is used, always install a thermal relay (THR) between the Inverter and the
motor and set n33 to 2 (no thermal protection).
In this case, program the sequence so that the magnetic contactor on the input side of
the main circuit is turned off by the contact of the thermal relay.
Design
Chapter 2
Summary of Contents for SYSDRIVE 3G3JV-AB001
Page 1: ...USER S MANUAL FIRST DRAFT SYSDRIVE 3G3JV Compact Simplified Inverter Cat No I528 E1 1...
Page 3: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Page 9: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 43: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Page 52: ...3 10 Preparing for Operation and Monitoring Chapter 3...
Page 53: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 62: ...4 10 Test Run Chapter 4...
Page 131: ...7 22 Maintenance Operations Chapter 7...
Page 132: ...Chapter 8 Specifications 8 1 Inverter Specifications 8 2 Option Specifications 8...
Page 138: ...Chapter 9 List of Parameters 9...
Page 150: ...Chapter 10 Using the Inverter for a Motor 10...
Page 165: ...Revision History 10 2...
Page 166: ...Cat No I528 E1 1 SYSDRIVE 3G3JV Compact Simplified Inverter USER S MANUAL...