2-33
D
Wiring the Power Supply
Make sure that the Inverter and Noise Filter are grounded together.
•
Always connect the power input terminals (R/L1, S/L2, and T/L3) and power supply via
a dedicated Noise Filter.
•
Reduce the length of the ground wire as much as possible.
•
Locate the Noise Filter as close as possible to the Inverter. Make sure that the cable
length between the Noise Filter and the Inverter does not exceed 40 cm.
•
The following Noise Filters are available (all footprint type).
3-phase 200-VAC Noise Filter
Inverter
3-phase 200-VAC Noise Filter
Model 3G3JV-
Model 3G3JV-
Rated current (A)
A2001/A2002/A2004/A2007
PFI2010-E
10
A2015/A2022
PFI2020-E
20
Single-phase 200-VAC Noise Filter
Inverter
Single-phase 200-V Noise Filter
Model 3G3JV-
Model 3G3JV-
Rated current (A)
AB001/AB002/AB004
PFI1010-E
10
AB007/AB015
PFI1020-E
20
D
Connecting a Motor to the Inverter
•
When connecting a motor to the Inverter, be sure to use a cable with a braided shield.
•
Reduce the length of the cable as short as possible and ground the shield on the Invert-
er side as well as the motor side. Make sure that the cable length between the Inverter
and the motor does not exceed 20 cm. Furthermore, connect a clamp core (Clamp Fil-
ter) close to the output terminals of the Inverter.
Product
Model
Manufacturer
Clamp Filter
2CAT3035-1330
TDK
D
Wiring a Control Cable
•
Be sure to connect a cable with a braided shield to the control circuit terminals.
•
Ground the shield on the Inverter side only.
Design
Chapter 2
Summary of Contents for SYSDRIVE 3G3JV-AB001
Page 1: ...USER S MANUAL FIRST DRAFT SYSDRIVE 3G3JV Compact Simplified Inverter Cat No I528 E1 1...
Page 3: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Page 9: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 43: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Page 52: ...3 10 Preparing for Operation and Monitoring Chapter 3...
Page 53: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 62: ...4 10 Test Run Chapter 4...
Page 131: ...7 22 Maintenance Operations Chapter 7...
Page 132: ...Chapter 8 Specifications 8 1 Inverter Specifications 8 2 Option Specifications 8...
Page 138: ...Chapter 9 List of Parameters 9...
Page 150: ...Chapter 10 Using the Inverter for a Motor 10...
Page 165: ...Revision History 10 2...
Page 166: ...Cat No I528 E1 1 SYSDRIVE 3G3JV Compact Simplified Inverter USER S MANUAL...