Selecting the Frequency Reference (n07) in Local Mode
•
Select the input method of frequency references in local mode.
•
Two frequency references are available in local mode. Select one of them according to
the application.
n07
Frequency Reference Selection in Local
Mode
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
The FREQ adjuster of the Digital Operator is enabled. (see note 1)
1
Key sequences on the Digital Operator are enabled. (see note 2)
Note 1. The maximum frequency (FMAX) is set when the FREQ adjuster is set to MAX.
Note 2. The frequency reference can be set with key sequences while the FREF indica-
tor is lit or with the set value in n21 for frequency reference 1. In either case, the
value is set in n21.
5-5-2 Upper and Lower Frequency Reference Limits
Regardless of the methods of operation mode and frequency reference in-
put, the upper and lower frequency reference limits can be set.
H
Setting the Upper and Lower Frequency Reference Limits
(n30 and n31)
•
Set the upper and lower frequency reference limits as percentage based on the maxi-
mum frequency as 100%.
n30
Upper Frequency Reference Limit
Changes during
operation
No
Setting
range
0% to 110%
(Max. frequency = 100%)
Unit of
setting
1%
Default setting
100
n31
Lower Frequency Reference Limit
Changes during
operation
No
Setting
range
0% to 110%
(Max. frequency = 100%)
Unit of
setting
1%
Default setting
0
Note If n31 is set to a value less than the minimum output frequency (FMIN), the Invert-
er will have no output when a frequency reference less than the minimum output
frequency input is ON.
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3JV-AB001
Page 1: ...USER S MANUAL FIRST DRAFT SYSDRIVE 3G3JV Compact Simplified Inverter Cat No I528 E1 1...
Page 3: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Page 9: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 43: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Page 52: ...3 10 Preparing for Operation and Monitoring Chapter 3...
Page 53: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 62: ...4 10 Test Run Chapter 4...
Page 131: ...7 22 Maintenance Operations Chapter 7...
Page 132: ...Chapter 8 Specifications 8 1 Inverter Specifications 8 2 Option Specifications 8...
Page 138: ...Chapter 9 List of Parameters 9...
Page 150: ...Chapter 10 Using the Inverter for a Motor 10...
Page 165: ...Revision History 10 2...
Page 166: ...Cat No I528 E1 1 SYSDRIVE 3G3JV Compact Simplified Inverter USER S MANUAL...