9-9
Pa-
ram-
eter
No.
Ref-
er-
ence
page
Changes
during
opera-
tion
Default
setting
Unit
of set-
ting
Set-
ting
range
Description
Name
17
Speed
search in
progress
ON: Speed search in prog-
ress
n41
Frequency
reference
gain
Used to the input characteristics of analog frequen-
cy references.
Gain: The frequency of maximum analog input (10
V or 20 mA) in percentage based on the maximum
0 to
255
1%
100
Yes
n42
Frequency
reference
bias
V or 20 mA) in percentage based on the maximum
frequency as 100%.
Bias: The frequency of minimum analog input (0 V
or 0 or 4 mA) in percentage based on the maxi-
mum frequency as 100%.
–99 to
99
1%
0
Yes
n43
Filter time
constant
settings
Used to set the digital filter with a first-order lag for
analog frequency references to be input.
0.00 to
2.00
0.01 s
0.10
No
n44
Analog mo-
tor output
Used to set the output frequency or current as a
monitored item.
0: Output frequency (10-V output at max. frequen-
cy with n45 set to 1.00).
1: Output current (10-V output with Inverter rated
output current with n45 set to 1.00)
0, 1
1
0
No
n45
Analog
monitor out-
put gain
Used to set the output characteristics of analog
monitor output.
0.00 to
2.00
0.01
1.00
Yes
n46
Carrier fre-
quency
selection
Used to set the carrier frequency.
Note
The default setting does not need any
changes in normal operation.
Note
Refer to
6-1 Setting the Carrier Frequency for
details.
1 to 4,
7 to 9
1
Varies
with
the ca-
pacity.
No
n47
Momentary
power inter-
ruption
compensa-
tion
Used to specify the processing that is performed
when a momentary power interruption occurs.
0: Inverter stops operating
1: Inverter continues operating if power interruption
is 0.5 s or less.
2: Inverter restarts when power is restored.
0 to 2
1
0
No
n48
Fault retry
Used to reset and restart the Inverter automatically
in the case the Inverter has an overvoltage fault,
overcurrent fault, or ground fault.
0 to 10
1
0
No
n49
Jump fre-
quency 1
Used to set the frequency jump function.
Output
frequency
n51
0.0 to
400
0.1 Hz
(see
note)
0.0
No
n50
Jump fre-
quency 2
Frequency
reference
0.0 to
400
0.1 Hz
(see
note)
0.0
No
n51
Jump width
Note
These values must satisfy the following
condition: n49
y
n50
n50
n49
0.0 to
25.5
0.1 Hz
0.0
No
List of Parameters
Chapter 9
Summary of Contents for SYSDRIVE 3G3JV-AB001
Page 1: ...USER S MANUAL FIRST DRAFT SYSDRIVE 3G3JV Compact Simplified Inverter Cat No I528 E1 1...
Page 3: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Page 9: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 43: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Page 52: ...3 10 Preparing for Operation and Monitoring Chapter 3...
Page 53: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 62: ...4 10 Test Run Chapter 4...
Page 131: ...7 22 Maintenance Operations Chapter 7...
Page 132: ...Chapter 8 Specifications 8 1 Inverter Specifications 8 2 Option Specifications 8...
Page 138: ...Chapter 9 List of Parameters 9...
Page 150: ...Chapter 10 Using the Inverter for a Motor 10...
Page 165: ...Revision History 10 2...
Page 166: ...Cat No I528 E1 1 SYSDRIVE 3G3JV Compact Simplified Inverter USER S MANUAL...