Grounding the Shield
In order to ground the shield securely, it is recommended that a cable clamp be directly
connected to the ground plate as shown below.
Ground plate
Cable clamp
Cable
Shield
H
LVD Conformance
•
Always connect the Inverter and power supply via a molded case circuit breaker
(MCCB) suitable to the Inverter for protecting the Inverter from damage that may result
from short-circuiting.
•
Use one MCCB per Inverter.
•
Select a suitable MCCB from the following table.
200-V Models
Inverter
MCCB (Mitsubishi Electric)
Model 3G3JV-
Type
Rated current (A)
A2001
NF30
5
A2002
30
5
A2004
5
A2007
10
A2015
20
A2022
20
AB001
NF30
5
AB002
30
5
AB004
10
AB007
20
AB015
20
The frequency reference power supply (FS) of the Inverter is of basic insulation
construction. When connecting the Inverter to peripheral devices, be sure to increase
the degree of insulation.
Design
Chapter 2
Summary of Contents for SYSDRIVE 3G3JV-AB001
Page 1: ...USER S MANUAL FIRST DRAFT SYSDRIVE 3G3JV Compact Simplified Inverter Cat No I528 E1 1...
Page 3: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Page 9: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 43: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Page 52: ...3 10 Preparing for Operation and Monitoring Chapter 3...
Page 53: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 62: ...4 10 Test Run Chapter 4...
Page 131: ...7 22 Maintenance Operations Chapter 7...
Page 132: ...Chapter 8 Specifications 8 1 Inverter Specifications 8 2 Option Specifications 8...
Page 138: ...Chapter 9 List of Parameters 9...
Page 150: ...Chapter 10 Using the Inverter for a Motor 10...
Page 165: ...Revision History 10 2...
Page 166: ...Cat No I528 E1 1 SYSDRIVE 3G3JV Compact Simplified Inverter USER S MANUAL...