9-3
Parame-
ter No.
Refer-
ence
page
Changes
during
opera-
tion
Default
setting
Unit
of set-
ting
Set-
ting
range
Description
Name
n06
STOP/RESET
Key function
selection
Used to select the stop method in remote
mode with n02 for operation mode selec-
tion set to 1.
0: STOP/RESET Key of the Digital Opera-
tor enabled.
1: STOP/RESET Key of the Digital Opera-
tor disabled.
0, 1
1
0
No
n07
Frequency
selection in lo-
cal mode
Used to set the input method for the fre-
quency reference in local mode.
0: The FREQ adjuster of the Digital Opera-
tor enabled.
1: Key sequences on the Digital Operator
enabled.
0, 1
1
0
No
n08
Key sequential
frequency set-
ting
Used to enable the Enter Key for setting
the frequency reference with the Increment
and Decrement Keys.
0: The value is entered with the Enter Key
pressed.
1: The value is enabled when the value is
input.
0, 1
1
0
No
n09
Maximum fre-
quency (FMAX)
Used to set the V/f pattern as the basic
characteristic of the Inverter with output
voltage per frequency set.
50.0 to
400
0.1 Hz
(see
note)
60.0
No
n10
Maximum volt-
age (VMAX)
Output
voltage
1 to
255
1 V
200
No
n11
Maximum volt-
age frequency
(FA)
0.2 to
400
0.1 Hz
(see
note)
60.0
No
n12
Middle output
frequency (FB)
Frequency
(Hz)
0.1 to
399
0.1 Hz
(see
note)
1.5
No
n13
Middle output
frequency volt-
age (VC)
Note
Set the parameters so that the fol-
lowing condition will be satisfied.
n14
x
n12 < n11
x
n09
1 to
255
1 V
12
No
n14
Minimum output
frequency
(FMIN)
n14
x
n12 < n11
x
n09
Note
The value set in n15 will be ignored if
parameters n14 and n12 are the
0.1 to
10.0
0.1 Hz
1.5
No
n15
Minimum output
frequency volt-
age (VMIN)
parameters n14 and n12 are the
same in value.
1 to 50
1 V
12.0
No
n16
Acceleration
time 1
Acceleration time: The time required to go
from 0% to 100% of the maximum fre-
quency.
0.0 to
999
0.1 s
10.0
Yes
n17
Deceleration
time 1
Deceleration time: The time required to go
from 100% to 0% of the maximum frequen-
cy.
Note
The actual acceleration or decel-
10.0
Yes
n18
Acceleration
time 2
Note
The actual acceleration or decel-
eration time is obtained from the
following formula.
Acceleration/Deceleration time =
10.0
Yes
n19
Deceleration
time 2
Acceleration/Deceleration time =
(Acceleration/Deceleration time
set value)
×
(Frequency reference
value)
÷
(Max. frequency)
10.0
Yes
List of Parameters
Chapter 9
Summary of Contents for SYSDRIVE 3G3JV-AB001
Page 1: ...USER S MANUAL FIRST DRAFT SYSDRIVE 3G3JV Compact Simplified Inverter Cat No I528 E1 1...
Page 3: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Page 9: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 43: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Page 52: ...3 10 Preparing for Operation and Monitoring Chapter 3...
Page 53: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 62: ...4 10 Test Run Chapter 4...
Page 131: ...7 22 Maintenance Operations Chapter 7...
Page 132: ...Chapter 8 Specifications 8 1 Inverter Specifications 8 2 Option Specifications 8...
Page 138: ...Chapter 9 List of Parameters 9...
Page 150: ...Chapter 10 Using the Inverter for a Motor 10...
Page 165: ...Revision History 10 2...
Page 166: ...Cat No I528 E1 1 SYSDRIVE 3G3JV Compact Simplified Inverter USER S MANUAL...