21
The circuit in the table below is used to interface phase inputs A, A, B, B, Z, and Z
(for the X and Y).
Item
Specification
Circuit Configuration
Signal level
EIA RS-422-A
Standards
5 V
Input impedance
220
Ω
Phase A, B, or Z
Phase A, B, or Z
1/2W
220
Ω
Response frequency
250 kpps max.
Phase A, B, or Z
Line receiver
The circuit in the table below is used to interface outputs OUT (X and Y).
Item
Specification
Circuit Configuration
Output voltage
0 to
±
10 V
+15 V
X to Y OUT
Load impedance
10 K
Ω
min.
–15 V
X to Y AGND
Interface Circuits
Section 2-4
Summary of Contents for C200H-MC221 -
Page 1: ...Cat No W315 E1 03 Motion Control Unit C200H MC221 OPERATION MANUAL ...