Appendix A
Control Bit/Flag Timing Charts
233
26. Cycle Start Bit, Forced Block End Bit, Task Error Flag, and Task Error Reset Bit
Forced Block End Bit
Operation
Task Error Flag
Cycle Start Bit
Task Error Reset Bit
Operation is stopped with the Forced Block End Bit and then a task error occurs. Correct the cause of the error,
clear the error by turning ON the Task Error Reset Bit, and restart the program by toggling the Cycle Start Bit.
27. Cycle Start Bit, Task Error Flag, and Task Error Reset Bit
Error Flag
Operation
Cycle Start Bit
Error Reset Bit
After a task error occurs, the Task Error Reset Bit and Cycle Start Bit are turned ON at the same time, clearing the
error and restarting operation simultaneously.
28. Automatic/Manual Mode Bit, Cycle Start Bit, Jogging Bit, and Manual Mode Flag
Cycle Start Bit
Operation
Jogging Bit
Automatic/Manual Mode Bit
Manual Mode Flag
The Automatic/Manual Mode Bit is turned OFF while the program is being executed, switching the Unit to manual
mode. Switching to manual mode causes the program to stop and axes to decelerate to a stop, but the Manual
Mode Flag is OFF while the axes are decelerating so the Jogging Bit signal is invalid.
The Manual Mode Flag will be turned ON when positioning is completed after decelerating to a stop. The Jogging
Bit signal can be received once the Manual Mode Flag is ON.
Summary of Contents for C200H-MC221 -
Page 1: ...Cat No W315 E1 03 Motion Control Unit C200H MC221 OPERATION MANUAL ...
Page 2: ......
Page 3: ...C200H MC221 Motion Control Unit Operation Manual Details Revised June 2010 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 10: ......
Page 12: ......
Page 16: ...xvi ...
Page 42: ......
Page 48: ......
Page 196: ......
Page 212: ......
Page 242: ......
Page 258: ......
Page 304: ......