11-16
For example, if the scan interval is 2 s, and the input value is 100 m
3
/min, a simple
summation would add 100 every 2 s resulting in 3000 after one minute. However, if the
computing unit is set to /min, then 2s/60s is multiplied every scan interval before the
value is added giving a result that is close to the actual input value. The scan interval
unit is in seconds.
OFF
∑
(measured value)
/S
∑
(measured value)
×
scan interval
/MIN
∑
(measured value)
×
scan interval/60
/HOUR
∑
(measured value)
×
scan interval/3600
For the setting procedure, see section 11.8.
About [Reset]
Whether or not to reset the computed result at every timeout is selectable. The figure
below shows the action of TLOG.SUM computation.
Example :
Result of the TLOG.SUM computation
Interval
1
2
3
Reset
Reset
Reset
Reset = On
Reset = Off
In case of TLOG.MAX computation, for example, the maximum value is derived for every
interval when “Reset” is “On,” and the maximum value from the start of computation is
derived when “Reset” is “Off.”
If Power is Lost while the TLOG Computation was in Progress
The TLOG computation is resumed when the power is restored. The operation varies
depending on whether power is restored before or after the scheduled time to create the
TLOG data.
Time of Recovery
TLOG Computation Operation
After the time to create
TLOG data are created immediately when power is
the TLOG data
restored. The measured/computed data up to the time of the power
disruption are used. At the next scheduled TLOG computation time,
data will be used from the point in time after the power was
restored.
Before the time to create
After power is restored, TLOG data are created at the normally
the TLOG data
scheduled time to perform the TLOG computation. All measured/
computed data excluding the power disruption period are used.
How the Measured/Computed Data are Handled when there is an Abnormality in the
Data
Type of Abnormal Data
Report Data
AVE
MAX/MIN/P-P
SUM
Positive overflow
not used
used
not used
Negative overflow
not used
used
not used
Error
not used
not used
not used
11.7 TLOG Computation
Summary of Contents for RD-MV100 Series
Page 40: ...1 22 This page intentionally left blank...
Page 41: ...1 23 Overview of Functions 1 This page intentionally left blank...
Page 139: ...7 5 Setting and Operating the Display 7 This page intentionally left blank...
Page 140: ...7 6 This page intentionally left blank...
Page 215: ...10 15 Other Functions 10 This page intentionally left blank...
Page 216: ...10 16 This page intentionally left blank...
Page 217: ...10 17 Other Functions 10 This page intentionally left blank...
Page 218: ...10 18 This page intentionally left blank...
Page 219: ...10 19 Other Functions 10 This page intentionally left blank...