5-12
5.
Upper and lower limits of scale
Set the upper and lower limits of the scale.
Pressing the [Input] soft key displays a window used to enter a numerical value.
Enter a value in the allowed range and press the DISP/ENTER key. For the
procedures related to entering numerical values, see “Entering Numbers” on
page 3-21.
• Allowed range : –30000 to 30000
• Decimal position :
The decimal can be set in the following positions : “
.
”
“
.
” “
.
” “
.
” “
”
• The decimal position is determined by the scale lower limit setting.
Note
•
Scale lower limit and scale upper limit cannot be set to the same value.
•
The recorder converts the measured data within a value span derived by removing the
decimal from the scaling upper and lower limits. In other words, conversion is performed by
using a span of 10 if the scale setting is –5 to 5, and 100 if the scale setting is –5.0 to 5.0.
The resolution of the value derived by using a span of 10 is coarser than the value derived
using a span of 100. Because the display becomes rough, set this value so that it is greater
than 100.
6.
Unit
Set the unit.
Pressing the [Input] soft key displays a window used to enter a character string.
Enter the unit (up to 6 alphanumeric characters) and press the DISP/ENTER
key. For the procedures related to entering character strings, see “Entering
Characters” on page 3-22.
Confirming operation
To confirm the new settings, press the DISP/ENTER key.
To cancel the new settings, press the ESC key. A window appears for you to confirm the
cancellation. Select “YES” using the arrow keys and press the DISP/ENTER key.
Explanation
For the range, and measurable range, see section 5.1, “Voltage Input Setting.”
Computing equation
The RD-MV100 uses the following square-root computation :
Using the following definitions :
• V
min
: Lower limit of span
• V
max
: Upper limit of span
• F
min
: Lower limit of scale
• F
max
: Upper limit of scale
• V
x
: Input voltage
• F
x
: Scaling value
V – V
V – V
+ F
x
max
min
max
F = (F – F )
x
min
min
min
When the value inside the square root is negative,
when Fmin < Fmax, Fx = negative overflow “–
”
when Fmin > Fmax, Fx = positive overflow “+
”
5.6 Square Root Computation Setting
Summary of Contents for RD-MV100 Series
Page 40: ...1 22 This page intentionally left blank...
Page 41: ...1 23 Overview of Functions 1 This page intentionally left blank...
Page 139: ...7 5 Setting and Operating the Display 7 This page intentionally left blank...
Page 140: ...7 6 This page intentionally left blank...
Page 215: ...10 15 Other Functions 10 This page intentionally left blank...
Page 216: ...10 16 This page intentionally left blank...
Page 217: ...10 17 Other Functions 10 This page intentionally left blank...
Page 218: ...10 18 This page intentionally left blank...
Page 219: ...10 19 Other Functions 10 This page intentionally left blank...