Corrosive Environment
Chapter 3: Site Preparation
Corrosive Environment
The equipment should not be directly exposed to corrosive environments. If the equipment
site is located in a coastal environment, proper air
fi
ltration for the site should be in place
to protect the equipment from salt mist contamination.
Air Quality
For cabinet-mounted equipment operating in an area, which is not environmentally controlled, the airborne
particulates level must not exceed concentration de
fi
ned in ETSI norm EN300 019 1–3 Class 3.
Salt mist like sea salt and road salt excluded and shall always be avoided.
Electrical Requirements
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
All electrical wiring for the MTS site must meet the requirements of any
and all applicable local codes and regulations.
Any device (that is power supply) providing isolation between the AC mains
and the MTS must provide reinforced insulation to hazardous voltages. The
DC power source providing power to the MTS shall comply with requirements
specified for a safety extra low voltage circuit (SELV) per EN60950.
The battery installation need a short circuit protection closest to the batteries.
The batteries should be installed in the same building and properly ventilated.
3-14
6802800U74-N September 2009
Summary of Contents for DIMETRA MTS 2
Page 4: ...This page intentionally left blank ...
Page 28: ...List of Procedures This page intentionally left blank xxii 6802800U74 N September 2009 ...
Page 30: ...List of Processes This page intentionally left blank xxiv 6802800U74 N September 2009 ...
Page 486: ...This page intentionally left blank A 10 6802800U74 N September 2009 ...
Page 492: ...This page intentionally left blank B 6 6802800U74 N September 2009 ...
Page 496: ...This page intentionally left blank C 4 6802800U74 N September 2009 ...