![Mitsubishi Electric MR-MQ100 User Manual Download Page 251](http://html.mh-extra.com/html/mitsubishi-electric/mr-mq100/mr-mq100_user-manual_1811809251.webp)
15 - 6
15 EMC DIRECTIVES
(3) Cable clamp
It is also possible to ground the exposed shielded part of the cable to the panel
with the cable clamp.
• Ground the shield at a position 20 to 30cm (7.87 to 11.81 inch) away from the
module.
• When the cables pulled out from the control panel, ground the cables at a
position 5 to 10cm (1.97 to 3.94inch) near the input/output hole of the control
panel with the cable clamp.
AD75CK
AD75CK
Inside control panel
Motion controller
5 to 10cm
(1.97 to 3.94 inch)
20 to 30cm
(7.87 to 11.81 inch)
• Cable clamp (Recommended product)
Manufacturer Model
name
AERSBAN-DSET
AERSBAN-ESET
Mitsubishi electric
AD75CK
Summary of Contents for MR-MQ100
Page 1: ......
Page 19: ...A 18 MEMO ...
Page 73: ...3 12 3 DESIGN MEMO ...
Page 97: ...5 8 5 TRIAL OPERATION AND ADJUSTMENT MEMO ...
Page 159: ...7 36 7 POSITIONING DEDICATED SIGNALS MEMO ...
Page 167: ...8 8 8 PARAMETERS FOR POSITIONING CONTROL MEMO ...
Page 189: ...9 22 9 SERVO PROGRAMS FOR POSITIONING CONTROL MEMO ...
Page 205: ...10 16 10 MOTION SFC PROGRAMS MEMO ...
Page 245: ...14 4 14 ERROR CODE MEMO ...
Page 253: ...15 8 15 EMC DIRECTIVES MEMO ...
Page 267: ...App 14 APPENDICES MEMO ...
Page 270: ......
Page 271: ......