[8] Characteristics of the Conventional and the New Refrigerants
1. Chemical
property
As with R22, the new refrigerant (R407C) is low in toxicity and chemically stable nonflammable refrigerant.
However, because the specific gravity of vapor refrigerant is greater than that of air, leaked refrigerant in a closed room will
accumulate at the bottom of the room and may cause hypoxia.
If exposed to an open flame, refrigerant will generate poisonous gases. Do not perform installation or service work in a con-
fined area.
*1 When CFC11 is used as a reference
*2 When CO
2
is used as a reference
2. Pressure
characteristics
The pressure in the system using R407C is 1.1 times as great as that in the system using R22.
New Refrigerant (HFC type)
Conventional Refriger-
ant (HCFC type)
R410A
R407C
R22
R32/R125
R32/R125/R134a
R22
Composition (wt%)
(50/50)
(23/25/52)
(100)
Type of Refrigerant
Pseudo-azeotropic
Refrigerant
Non-azeotropic
Refrigerant
Single Refrigerant
Chloride
Not included
Not included
Included
Safety Class
A1/A1
A1/A1
A1
Molecular Weight
72.6
86.2
86.5
Boiling Point (°C/°F)
-51.4/-60.5
-43.6/-46.4
-40.8/-41.4
Steam Pressure
(25°C,MPa/77°F,psi) (gauge)
1.557/226
0.9177/133
0.94/136
Saturated Steam Density
(25°C,kg/m
3
/77°F,psi)
64.0
42.5
44.4
Flammability
Nonflammable
Nonflammable
Nonflammable
Ozone Depletion Coefficient (ODP)
*1
0
0
0.055
Global Warming Coefficient (GWP)
*2
1975
1653
1700
Refrigerant Charging Method
Refrigerant charging in
the liquid state
Refrigerant charging in
the liquid state
Refrigerant charging in
the gaseous state
Replenishment of Refrigerant after a Refrigerant
Leak
Available
Available
Available
Temperature (°C/°F)
Saturation Pressure (gauge)
R410A
R407C
R22
MPa/psi
MPa/psi
MPa/psi
-20/-4
0.30/44
0.18/26
0.14/20
0/32
0.70/102
0.47/68
0.40/58
20/68
1.34/194
0.94/136
0.81/117
40/104
2.31/335
1.44/209
1.44/209
60/140
3.73/541
2.43/354
2.33/338
65/149
4.17/605
2.74/399
2.60/377
Summary of Contents for CAHV-P500YA-HPB
Page 1: ...Service Handbook Service Handbook CAHV P500YA HPB Model 2011 HOT WATER HEAT PUMP ...
Page 7: ...CONTENTS HWE10060 GB ...
Page 9: ... 2 HWE10060 GB ...
Page 19: ... 12 HWE10060 GB ...
Page 37: ... 30 HWE10060 GB ...
Page 46: ... 39 HWE10060 GB IV Remote Controller 1 Using the Remote Controller 41 2 Function Settings 46 ...
Page 47: ... 40 HWE10060 GB ...
Page 55: ... IV Remote Controller 48 HWE10060 GB ...
Page 56: ... 49 HWE10060 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 51 ...
Page 57: ... 50 HWE10060 GB ...
Page 61: ... V Electrical Wiring Diagram 54 HWE10060 GB ...
Page 63: ... 56 HWE10060 GB ...
Page 67: ... VI Refrigerant Circuit 60 HWE10060 GB ...
Page 69: ... 62 HWE10060 GB ...
Page 101: ... VII Control 94 HWE10060 GB ...
Page 103: ... 96 HWE10060 GB ...
Page 109: ... VIII Test Run Mode 102 HWE10060 GB ...
Page 111: ... 104 HWE10060 GB ...
Page 155: ... IX Troubleshooting 148 HWE10060 GB ...
Page 156: ... 149 HWE10060 GB X Attachments 1 R407C saturation temperature table 151 ...
Page 157: ... 150 HWE10060 GB ...
Page 159: ... X Attachments 152 HWE10060 GB ...