VII
Control ]
- 79 -
HWE10060
GB
[2] Operating characteristics and Control Capabilities
Outline of Control Method
-1- Operating characteristics
Function
Component
Symbol
Control/
Detection
Ac-
tion
Unit
Trigger condition
Unit
protection
Pressure
switch
High-pressure
switch
63H1
HP 63H1
ON
MPa
(2.95)
OFF MPa
3.85
High-pressure
sensor
63HS
HP 63HS
OFF MPa
-
Low-pressure
sensor
63LS
LP 63LS
OFF MPa
The low pressure has dropped below 0.06 MPa
within 30 seconds of compressor start-up.
The low pressure has dropped below 0.06 MPa
within 30 seconds of a defrost cycle.
During water heating, the low pressure has
dropped by 0.02 MPa after the air-side heat ex-
changer inlet temperature has reached -31ºC.
During water heating, the low pressure has
dropped by 0.02 MPa after the air-side suction
pipe temperature has reached -33ºC.
The outside temperature of 10ºC or above has
been detected for 20 minutes and the low pres-
sure has dropped below 0.06 MPa during water
heating.
Compressor overcurrent relay
Compressor
current
OFF
A
33
Built-in thermistor on the fan
motor (Stops the motor)
Built-in
thermistor on
the fan motor
ON
ºC
90 15
OFF
ºC
145 5
Thermis-
tor
Discharge refrig-
erant temp.
(Discharge temp.
overrise protec-
tion)
TH1
TH5
Discharge
gas temp.
OFF
ºC
A discharge gas temperature of 120ºC or above
has been detected for 30 seconds while the com-
pressor is in operation. (Preliminary abnormal
stop)
If this happens three times, the unit will make an
abnormal stop.
If a discharge gas temperature of 125ºC or above
was detected, the unit will make an abnormal
stop.
Air-side HEX inlet
temp.
(vacuum protec-
tion)
TH4
TH8
Air-side HEX
inlet temp.
OFF
ºC
A heat-side heat exchanger inlet temperature of
-33ºC was detected.
Suction temp.
(vacuum and
freeze-up protec-
tion)
TH2
TH6
Suction gas
temp.
OFF
ºC
A suction gas temperature of -36ºC was detected.
Compressor shell
temp.
(compressor
floodback protec-
tion)
TH3
TH7
Comp. shell
temp.
OFF
ºC
A shell bottom SH temperature of 10ºC or below
has been detected for 40 minutes while the com-
pressor is in operation.
Inverter heatsink
temp
THHS
INV. heat-
sink temp.
OFF
ºC
A temperature of 80ºC or above has been detected
for 10 minutes or a temperature of 90ºC or above
was detected.
Refrigerant
circuit
control
Liquid injection circuit
LEV2
SV2
Discharge
gas temp.
ºC
Injection is controlled by referencing the discharge
gas temperature.
Pump
control
Inlet (freeze-up protection)
TH10
TH12
Water inlet
ON
ºC
3
OFF
ºC
5
Outside temperature thermis-
tor
TH9
Outside
temp.
ON
ºC
1
OFF
ºC
3
Freeze-up protection circuit
The pump turns on when the water inlet tempera-
ture has reached below the "ON" threshold AND
the outside temperature has reached below the
"ON" threshold when the compressor is stopped.
Summary of Contents for CAHV-P500YA-HPB
Page 1: ...Service Handbook Service Handbook CAHV P500YA HPB Model 2011 HOT WATER HEAT PUMP ...
Page 7: ...CONTENTS HWE10060 GB ...
Page 9: ... 2 HWE10060 GB ...
Page 19: ... 12 HWE10060 GB ...
Page 37: ... 30 HWE10060 GB ...
Page 46: ... 39 HWE10060 GB IV Remote Controller 1 Using the Remote Controller 41 2 Function Settings 46 ...
Page 47: ... 40 HWE10060 GB ...
Page 55: ... IV Remote Controller 48 HWE10060 GB ...
Page 56: ... 49 HWE10060 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 51 ...
Page 57: ... 50 HWE10060 GB ...
Page 61: ... V Electrical Wiring Diagram 54 HWE10060 GB ...
Page 63: ... 56 HWE10060 GB ...
Page 67: ... VI Refrigerant Circuit 60 HWE10060 GB ...
Page 69: ... 62 HWE10060 GB ...
Page 101: ... VII Control 94 HWE10060 GB ...
Page 103: ... 96 HWE10060 GB ...
Page 109: ... VIII Test Run Mode 102 HWE10060 GB ...
Page 111: ... 104 HWE10060 GB ...
Page 155: ... IX Troubleshooting 148 HWE10060 GB ...
Page 156: ... 149 HWE10060 GB X Attachments 1 R407C saturation temperature table 151 ...
Page 157: ... 150 HWE10060 GB ...
Page 159: ... X Attachments 152 HWE10060 GB ...