VIII
Test Run Mode ]
- 101 -
HWE10060
GB
[4] Refrigerant
[5] Symptoms that do not Signify Problems
[6] Standard operating characteristics(Reference data)
Reference data
Space
requirements
DB
°C
7
16
Ambient
temperature
WB
°C
6
12.4
Temperature
Discharge refrigerant
°C
75
72
Suction refrigerant
°C
6
10
Shell temperature
°C
20
35
Air-side heat exchanger inlet
°C
1
7
Outside temperature
°C
7
16
Inlet water temperature
°C
40
40
Outlet water temperature
°C
45
45
Pressure
High pressure
MPa
1.72
1.72
Low pressure
MPa
0.38
0.47
LEV opening
Main circuit
pulse
550
870
Injection
pulse
60
60
Compressor
Frequency
Hz
73
59
Fan
Frequency
Hz
55
50
Unit type
CAHV-P500YA-HPB
Refrigerant type
R407C
Refrigerant charge
5.5kg × 2
If terminals 19 and 20 on TB5 are short-circuited,
the fan will be forced to operate even after the
compressor has stopped.
Cause
Remote controller display
Symptom
Fan does not stop while stopping op-
eration.
The display shown right will appear
on the unit remote controller for
about 5 minutes when the main
power source is turned on.
Extinguished
"PLEASE WAIT" ("HO")
blinking display
The system is under starting up.
Operate the remote controller after the blinking of
“PLEASE WAIT” (“HO”) is disappeared.
Summary of Contents for CAHV-P500YA-HPB
Page 1: ...Service Handbook Service Handbook CAHV P500YA HPB Model 2011 HOT WATER HEAT PUMP ...
Page 7: ...CONTENTS HWE10060 GB ...
Page 9: ... 2 HWE10060 GB ...
Page 19: ... 12 HWE10060 GB ...
Page 37: ... 30 HWE10060 GB ...
Page 46: ... 39 HWE10060 GB IV Remote Controller 1 Using the Remote Controller 41 2 Function Settings 46 ...
Page 47: ... 40 HWE10060 GB ...
Page 55: ... IV Remote Controller 48 HWE10060 GB ...
Page 56: ... 49 HWE10060 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 51 ...
Page 57: ... 50 HWE10060 GB ...
Page 61: ... V Electrical Wiring Diagram 54 HWE10060 GB ...
Page 63: ... 56 HWE10060 GB ...
Page 67: ... VI Refrigerant Circuit 60 HWE10060 GB ...
Page 69: ... 62 HWE10060 GB ...
Page 101: ... VII Control 94 HWE10060 GB ...
Page 103: ... 96 HWE10060 GB ...
Page 109: ... VIII Test Run Mode 102 HWE10060 GB ...
Page 111: ... 104 HWE10060 GB ...
Page 155: ... IX Troubleshooting 148 HWE10060 GB ...
Page 156: ... 149 HWE10060 GB X Attachments 1 R407C saturation temperature table 151 ...
Page 157: ... 150 HWE10060 GB ...
Page 159: ... X Attachments 152 HWE10060 GB ...