IX
Troubleshooting ]
- 137 -
HWE10060
GB
Outdoor Unit Fan
-7- Fan
The rotation speed of the fan is controlled by the inverter. Check the inverter output status on the LED to check the rotation
speed. The maximum rotation speed of the fan is approximately 670 rpm. Make appropriate settings on the display function
to get the output to be displayed [%]. Refer to section 2 "Checking the sensor status" for how to use the display function.
(page107) 73% indicates that the fan is operating at full speed, and 0% indicates that the fan is stopped.
The rotation speed of the fan changes according to the number of units in operation. If the fan does not operate or if it vibrates,
FAN INV board problem or fan motor error is suspected. Refer to section -5-(2) [5] Check the fan motor ground fault or the
winding. and section [6] Check the fan inverter board failure."
-8- Troubleshooting
1. Important notes
If the unit or its refrigerant circuit components experience malfunctions, take the following steps to prevent recurrence.
(1) Diagnose the problem and find the cause.
(2) Before repairing leaks on the brazed sections on the pipes, recover the refrigerant. Braze under nitrogen purge to prevent
oxidation.
(3) If any component (including the compressor) malfunctions, only replace the affected parts; it is not necessary to replace
the entire unit.
(4) Be sure to recover the refrigerant from the unit before disposing of the unit.
(5) If the cause of the problem cannot be identified, contact the service desk with the following information: unit model, serial
number, and the nature of the problem.
2. Before replacing the fan
(1) Before replacing the fan, turn off the main power of the unit.
(2) The motor connectors are on the FAN INV board in the control box and can be accessed by removing the service panel
and the fan guard.
(3) Install the fan wires as they were, using the same route and all required clamps.
Summary of Contents for CAHV-P500YA-HPB
Page 1: ...Service Handbook Service Handbook CAHV P500YA HPB Model 2011 HOT WATER HEAT PUMP ...
Page 7: ...CONTENTS HWE10060 GB ...
Page 9: ... 2 HWE10060 GB ...
Page 19: ... 12 HWE10060 GB ...
Page 37: ... 30 HWE10060 GB ...
Page 46: ... 39 HWE10060 GB IV Remote Controller 1 Using the Remote Controller 41 2 Function Settings 46 ...
Page 47: ... 40 HWE10060 GB ...
Page 55: ... IV Remote Controller 48 HWE10060 GB ...
Page 56: ... 49 HWE10060 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 51 ...
Page 57: ... 50 HWE10060 GB ...
Page 61: ... V Electrical Wiring Diagram 54 HWE10060 GB ...
Page 63: ... 56 HWE10060 GB ...
Page 67: ... VI Refrigerant Circuit 60 HWE10060 GB ...
Page 69: ... 62 HWE10060 GB ...
Page 101: ... VII Control 94 HWE10060 GB ...
Page 103: ... 96 HWE10060 GB ...
Page 109: ... VIII Test Run Mode 102 HWE10060 GB ...
Page 111: ... 104 HWE10060 GB ...
Page 155: ... IX Troubleshooting 148 HWE10060 GB ...
Page 156: ... 149 HWE10060 GB X Attachments 1 R407C saturation temperature table 151 ...
Page 157: ... 150 HWE10060 GB ...
Page 159: ... X Attachments 152 HWE10060 GB ...