IX
Troubleshooting ]
- 120 -
HWE10060
GB
DCCT sensor/circuit fault
●DCCT sensor fault
●INV board fault
Open-circuited IPM/Disconnected ACCT sensor
●ACCT sensor fault
●Broken compressor wiring
●Inverter circuit fault (IPM fault)
Incorrect wiring
●ACCT sensor fault
THHS sensor/circuit fault
●THHS sensor fault
(Thermistor fault, pinched lead wire, missing pins on
the connectors)
●Thermistor input circuit fault on the circuit board
●INV board fault
Serial communication error
●Communication error between control board and
INV board (noise interference, broken wiring)
IPM system error
●INV board switch setting error
●Wiring or connector connection failure between
connectors on IPM-driven power supply circuit
●INV board fault
-
(Preliminary : 4300)
Address overlap
●There are two or more of the same address.
6830
Non-consecutive address, system error
●Address setting error (Non-consecutive address)
7105
Remote controller signal reception error 1
●Remote controller cables are not connected.
●Broken wiring
●Broken remote controller wiring
●Communication circuit fault on the control board
6831
Remote controller signal transmission error
●Communication error due to external noise interference
●Communication circuit fault on the control board
6832
Remote controller signal reception error 2
●Communication error due to external noise interference
●Communication circuit fault on the control board
6834
Address setting error
●Address setting error (Non-consecutive address)
7105
Incompatible combination of units
●Different types of units are connected to the same
system.
7130
No.-of-connected-unit setting is incorrect
●No.-of-connected-unit setting is incorrect (Main unit)
7102
Communication error between Main & Sub units
Communication error between the MAIN and SUB circuits
●Connector contact failure at CN102 on the control board
●Contact failure at the MA-MB terminal block on the
MAIN circuit or terminal block TB3 on the SUB circuit.
6500
Inverter fault
Remote controller error
(incl. remote controller
wiring fault)
Multiple unit
system error
5301
5305
(Preliminary : 4300)
(Preliminary : 4305)
(Details : 118)
5301
5305
(Preliminary : 4300)
(Preliminary : 4305)
(Details : 119)
5301
5305
(Preliminary : 4300)
(Preliminary : 4305)
(Details : 120)
5110
(Preliminary : 1214)
(Details COMP : 01)
(Details FAN : 05)
0403
(Preliminary : 4300)
(Preliminary : 4305)
(Details COMP : 01)
(Details FAN : 05)
*Preliminary error codes will not appear on the 7-segment LED.
Error Type
Cause
(problem with the installation
environment/setting error)
Cause
(component problem)
Error Code
Circuit board
Remote controller
Resetting the error
Unit side
(Circuit
board)
Remote
SWS1
Operation SW
Summary of Contents for CAHV-P500YA-HPB
Page 1: ...Service Handbook Service Handbook CAHV P500YA HPB Model 2011 HOT WATER HEAT PUMP ...
Page 7: ...CONTENTS HWE10060 GB ...
Page 9: ... 2 HWE10060 GB ...
Page 19: ... 12 HWE10060 GB ...
Page 37: ... 30 HWE10060 GB ...
Page 46: ... 39 HWE10060 GB IV Remote Controller 1 Using the Remote Controller 41 2 Function Settings 46 ...
Page 47: ... 40 HWE10060 GB ...
Page 55: ... IV Remote Controller 48 HWE10060 GB ...
Page 56: ... 49 HWE10060 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 51 ...
Page 57: ... 50 HWE10060 GB ...
Page 61: ... V Electrical Wiring Diagram 54 HWE10060 GB ...
Page 63: ... 56 HWE10060 GB ...
Page 67: ... VI Refrigerant Circuit 60 HWE10060 GB ...
Page 69: ... 62 HWE10060 GB ...
Page 101: ... VII Control 94 HWE10060 GB ...
Page 103: ... 96 HWE10060 GB ...
Page 109: ... VIII Test Run Mode 102 HWE10060 GB ...
Page 111: ... 104 HWE10060 GB ...
Page 155: ... IX Troubleshooting 148 HWE10060 GB ...
Page 156: ... 149 HWE10060 GB X Attachments 1 R407C saturation temperature table 151 ...
Page 157: ... 150 HWE10060 GB ...
Page 159: ... X Attachments 152 HWE10060 GB ...