IX
Troubleshooting ]
- 107 -
HWE10060
GB
2. Checking the sensor status
Setting procedure
Step 1
Set the dip switches
SW2 and SW3.
Set the dip switches on the circuit board as follows to check temperatures and pres-
sures.
SW2
SW3
10
5
6
7
8
9
10
OFF
OFF
OFF
OFF
OFF
ON
ON
Step 2
Select the desired
item with the push
switch SWP3.
Press the push switch SWP3 to toggle through the item codes listed below.
Select an item code from c01 through c36, and press either of the push switches SWP1
or SWP2 to display the current temperature, pressure, and electrical current in blinking
form.
Step 3
Press the push
switches SWP1 (
↑
) or
SWP2 (
↓
) to increase
or decrease the value.
Refer to "Sensors and item code list" for the types of errors that appear on error history.
Step 4
Press the push switch
SWP3 to save the
change.
Press SWP3 to stop the blinking and return to the item code display.
Summary of Contents for CAHV-P500YA-HPB
Page 1: ...Service Handbook Service Handbook CAHV P500YA HPB Model 2011 HOT WATER HEAT PUMP ...
Page 7: ...CONTENTS HWE10060 GB ...
Page 9: ... 2 HWE10060 GB ...
Page 19: ... 12 HWE10060 GB ...
Page 37: ... 30 HWE10060 GB ...
Page 46: ... 39 HWE10060 GB IV Remote Controller 1 Using the Remote Controller 41 2 Function Settings 46 ...
Page 47: ... 40 HWE10060 GB ...
Page 55: ... IV Remote Controller 48 HWE10060 GB ...
Page 56: ... 49 HWE10060 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 51 ...
Page 57: ... 50 HWE10060 GB ...
Page 61: ... V Electrical Wiring Diagram 54 HWE10060 GB ...
Page 63: ... 56 HWE10060 GB ...
Page 67: ... VI Refrigerant Circuit 60 HWE10060 GB ...
Page 69: ... 62 HWE10060 GB ...
Page 101: ... VII Control 94 HWE10060 GB ...
Page 103: ... 96 HWE10060 GB ...
Page 109: ... VIII Test Run Mode 102 HWE10060 GB ...
Page 111: ... 104 HWE10060 GB ...
Page 155: ... IX Troubleshooting 148 HWE10060 GB ...
Page 156: ... 149 HWE10060 GB X Attachments 1 R407C saturation temperature table 151 ...
Page 157: ... 150 HWE10060 GB ...
Page 159: ... X Attachments 152 HWE10060 GB ...