II
Restrictions ]
- 23 -
HWE10060
GB
(4) Re-initializing the system
When the settings for the items below have been changed, the system will require re-initialization.
• Dip switch SW2-8 (use or non-use of an external water temperature sensor) (Re-initialization is required only for
the Multiple system.)
• Dip switch SW2-9 (multiple unit control)
• Dip switch SW3-3 (water temperature control method)
• External signal input setting [107] (total number of units in the system)
• Rotary switches (SWU1 and SWU2) (unit address)
Take the following steps to re-initialize the system:
(1) Set the rotary switch SWU3 to "F."
[FFFF] will appear in the LED1.
(2) Press and hold the push switch SWP3 for one second or longer.
• While the system is starting up [9999] will appear on LED1.
• When start-up is complete, a control property [0012] will appear.
• Then, five seconds later, [FFFF] will appear.
(3) Press and hold the push switch SWP3 again for one second or longer.
• While the system is starting up [9999] will appear on LED1.
• When start-up is complete, a control property [0012] will appear.
• Then, five seconds later, [FFFF] will appear.
(4) Set the rotary switch SWU3 back to "0."
(5) Resetting the system (MAIN and SUB circuits)
Take the following steps to reset the system. An error can also be reset by taking the steps below.
Note that the errors on the MAIN unit must be reset through the MAIN circuit, and the errors on the sub unit must be
reset through the SUB circuit.
When an error on the MAIN unit is reset, all sub units will stop.
(1) Set the rotary switch SWU3 to "F."
[FFFF] will appear in the LED1.
(2) Press and hold the push switch SWP3 for one second or longer.
• While the system is starting up [9999] will appear on LED1.
• When start-up is complete, a control property [0012] will appear.
• Then, five seconds later, [FFFF] will appear.
(3) Set the rotary switch SWU3 back to "0."
Summary of Contents for CAHV-P500YA-HPB
Page 1: ...Service Handbook Service Handbook CAHV P500YA HPB Model 2011 HOT WATER HEAT PUMP ...
Page 7: ...CONTENTS HWE10060 GB ...
Page 9: ... 2 HWE10060 GB ...
Page 19: ... 12 HWE10060 GB ...
Page 37: ... 30 HWE10060 GB ...
Page 46: ... 39 HWE10060 GB IV Remote Controller 1 Using the Remote Controller 41 2 Function Settings 46 ...
Page 47: ... 40 HWE10060 GB ...
Page 55: ... IV Remote Controller 48 HWE10060 GB ...
Page 56: ... 49 HWE10060 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 51 ...
Page 57: ... 50 HWE10060 GB ...
Page 61: ... V Electrical Wiring Diagram 54 HWE10060 GB ...
Page 63: ... 56 HWE10060 GB ...
Page 67: ... VI Refrigerant Circuit 60 HWE10060 GB ...
Page 69: ... 62 HWE10060 GB ...
Page 101: ... VII Control 94 HWE10060 GB ...
Page 103: ... 96 HWE10060 GB ...
Page 109: ... VIII Test Run Mode 102 HWE10060 GB ...
Page 111: ... 104 HWE10060 GB ...
Page 155: ... IX Troubleshooting 148 HWE10060 GB ...
Page 156: ... 149 HWE10060 GB X Attachments 1 R407C saturation temperature table 151 ...
Page 157: ... 150 HWE10060 GB ...
Page 159: ... X Attachments 152 HWE10060 GB ...