II
Restrictions ]
- 25 -
HWE10060
GB
2. Notes on pipe corrosion
Water treatment and water quality control
Poor-quality circulating water can cause the water-side heat exchanger to scale up or corrode, reducing heat-
exchange performance. Properly control the quality of the circulating water.
• Removing foreign objects and impurities in the pipes
During installation, keep foreign objects, such as welding and sealant fragments and rust, out of the pipes.
• Water Quality Control
(1)
Poor-quality water can corrode or scale up the heat exchanger. Regular water treatment is recommended.
Water circulation systems using open heat storage tanks are particularly prone to corrosion.
When using an open heat storage tank, install a water-to-water heat exchanger, and use a closed-loop circuit
on the air-conditioner side. If a water supply tank is installed, keep contact with air to a minimum, and keep the
level of dissolved oxygen in the water no higher than 1 mg/ℓ.
(2) Water quality standard
Reference: Guideline of Water Quality for Refrigeration and Air Conditioning Equipment. (JRA GL02E-1994)
(3)
Please consult with a water quality control specialist about water quality control methods and water quality
calculations before using anti-corrosive solutions for water quality management.
(4)
When replacing an air conditioner (including when only the heat exchanger is replaced), first analyze the water
quality and check for possible corrosion.
Corrosion can occur in water systems in which there has been no signs of corrosion. If the water quality level
has dropped, adjust the water quality before replacing the unit.
Items
Lower mid-range temperature water system
Water Temp. ≤ 60ºC
Higher mid-range temperature water system
Water Temp. > 60ºC
Tendency
Recirculating water
Make-up water
Recirculating water
Make-up water
Corrosive
Scale-
forming
Standard
items
pH (25°C)
0
.
8
~
0
.
7
0
.
8
~
0
.
7
0
.
8
~
0
.
7
0
.
8
~
0
.
7
Electric conductivity
(mS/m) (25
°C)
30 or less
30 or less
30 or less
30 or less
(μs/cm) (25
°C)
[300 or less]
[300 or less]
[300 or less]
[300 or less]
Chloride ion
(mg Cl
-
/ℓ)
50 or less
50 or less
30 or less
30 or less
Sulfate ion
(mg SO4
2-
/ℓ)
50 or less
50 or less
30 or less
30 or less
Acid consumption
50 or less
50 or less
50 or less
50 or less
(pH4.8) (mg CaCO
3
/ℓ)
Total hardness
(mg CaCO
3
/ℓ)
70 or less
70 or less
70 or less
70 or less
Calcium hardness
(mg CaCO
3
/ℓ)
50 or less
50 or less
50 or less
50 or less
Ionic silica
(mg SiO
2
/ℓ)
30 or less
30 or less
30 or less
30 or less
Reference
items
/
e
F
g
m
(
n
o
r
I
ℓ)
1.0 or less
0.3 or less
1.0 or less
0.3 or less
Copper
(mg Cu/ℓ)
1.0 or less
1.0 or less
1.0 or less
1.0 or less
Sulfide ion
(mg S
2-
/ℓ) Not to be detected Not to be detected Not to be detected Not to be detected
Ammonium ion
(mg NH
4
+
/ℓ)
0.3 or less
0.1 or less
0.1 or less
0.1 or less
Residual chlorine
(mg Cl/ ℓ)
0.25 or less
0.3 or less
0.1 or less
0.3 or less
Free carbon dioxide
(mg CO
2
/ℓ)
0.4 or less
4.0 or less
0.4 or less
4.0 or less
—
—
—
—
x
e
d
n
i
y
t
il
i
b
a
t
s
r
e
n
z
y
R
Summary of Contents for CAHV-P500YA-HPB
Page 1: ...Service Handbook Service Handbook CAHV P500YA HPB Model 2011 HOT WATER HEAT PUMP ...
Page 7: ...CONTENTS HWE10060 GB ...
Page 9: ... 2 HWE10060 GB ...
Page 19: ... 12 HWE10060 GB ...
Page 37: ... 30 HWE10060 GB ...
Page 46: ... 39 HWE10060 GB IV Remote Controller 1 Using the Remote Controller 41 2 Function Settings 46 ...
Page 47: ... 40 HWE10060 GB ...
Page 55: ... IV Remote Controller 48 HWE10060 GB ...
Page 56: ... 49 HWE10060 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 51 ...
Page 57: ... 50 HWE10060 GB ...
Page 61: ... V Electrical Wiring Diagram 54 HWE10060 GB ...
Page 63: ... 56 HWE10060 GB ...
Page 67: ... VI Refrigerant Circuit 60 HWE10060 GB ...
Page 69: ... 62 HWE10060 GB ...
Page 101: ... VII Control 94 HWE10060 GB ...
Page 103: ... 96 HWE10060 GB ...
Page 109: ... VIII Test Run Mode 102 HWE10060 GB ...
Page 111: ... 104 HWE10060 GB ...
Page 155: ... IX Troubleshooting 148 HWE10060 GB ...
Page 156: ... 149 HWE10060 GB X Attachments 1 R407C saturation temperature table 151 ...
Page 157: ... 150 HWE10060 GB ...
Page 159: ... X Attachments 152 HWE10060 GB ...