Startup sequence rotation
-2- Initial control
When the power is turned on, the initial processing of the microcomputer is given top priority.
During the initial processing, processing of the operation signal is suspended and is resumed after the initial processing is
completed.
(Initial processing involves data processing by the microcomputer and initial setup of the LEV opening. This process takes up
to two minutes.)
During the initial processing ”
” will appear on the LED monitor on the MAIN board.
Initial Control
-3- Compressor frequency
The upper limit of frequency during the first 30 seconds of operation is 48 Hz.
The upper limit of frequency during the first 90 seconds of operation is 60 Hz.
If the water temperature is controlled based on the outlet water temperature (SW3-3 is set to OFF.), for 90 seconds after the
startup, the compressor will be controlled every 30 seconds so that the frequency fluctuation will be kept within ± 5 Hz.
If the water temperature is controlled based on the external water temperature sensor reading or the inlet water temperature
(SW3-3 is set to ON.), for 90 seconds after the startup, the compressor will be controlled every 30 seconds so that the fre-
quency fluctuation will be kept within ± 10 Hz.
(The above does not apply when the high-pressure is suppressed to protect the system or when the defrost operation is in
progress.)
The amount of frequency change is controlled to approximate the target value that are determined based on the temperature
difference between the current and the preset water temperatures.
The minimum operating frequency is 30 Hz.
The maximum frequency will be determined based on the relationship between the water temperature and the outside tem-
perature as well as the ON/OFF status of the Energy-save/Maximum capacity contact.
(The values not on listed in the table are interpolated.)
"Energy-save/Maximum capacity" contact is ON.
(
Maximum frequency of the compressor
Hz
)
°C
−
15
−
5
0
5
10
15
20
25
30
35 or above
35 or above
°C
35
100
100
100
77
65
57
53
49
46
43
45
100
100
100
82
69
60
55
51
48
44
60
100
100
100
88
76
69
63
58
53
49
70
100
−
20
100
100
100
100
100
100
95
84
75
68
62
57
50
"Energy-save/Maximum capacity" contact is OFF.
(
Maximum frequency of the compressor
Hz
)
−
15
−
5
0
5
10
15
20
25
30
35
100
100
100
100
91
85
81
76
71
66
45
100
100
100
100
94
88
83
78
73
67
60
100
100
100
100
100
93
87
81
75
69
70
100
−
20
100
100
100
100
100
100
100
100
96
90
83
77
71
Water
temperature
°C
Water
temperature
Outside temp.
°C
Outside temp.
Summary of Contents for CAHV-P500YA-HPB
Page 1: ...Service Handbook Service Handbook CAHV P500YA HPB Model 2011 HOT WATER HEAT PUMP ...
Page 7: ...CONTENTS HWE10060 GB ...
Page 9: ... 2 HWE10060 GB ...
Page 19: ... 12 HWE10060 GB ...
Page 37: ... 30 HWE10060 GB ...
Page 46: ... 39 HWE10060 GB IV Remote Controller 1 Using the Remote Controller 41 2 Function Settings 46 ...
Page 47: ... 40 HWE10060 GB ...
Page 55: ... IV Remote Controller 48 HWE10060 GB ...
Page 56: ... 49 HWE10060 GB V Electrical Wiring Diagram 1 Electrical Wiring Diagram 51 ...
Page 57: ... 50 HWE10060 GB ...
Page 61: ... V Electrical Wiring Diagram 54 HWE10060 GB ...
Page 63: ... 56 HWE10060 GB ...
Page 67: ... VI Refrigerant Circuit 60 HWE10060 GB ...
Page 69: ... 62 HWE10060 GB ...
Page 101: ... VII Control 94 HWE10060 GB ...
Page 103: ... 96 HWE10060 GB ...
Page 109: ... VIII Test Run Mode 102 HWE10060 GB ...
Page 111: ... 104 HWE10060 GB ...
Page 155: ... IX Troubleshooting 148 HWE10060 GB ...
Page 156: ... 149 HWE10060 GB X Attachments 1 R407C saturation temperature table 151 ...
Page 157: ... 150 HWE10060 GB ...
Page 159: ... X Attachments 152 HWE10060 GB ...