XGB Analog edition manual
3 - 22
3.12.2 Setting area of operation parameters
XBF-DV04A
Address
(Dec)
Description
Details
Remarks
0
Set up the run channel
Bit On(1): Run
Bit Off(0): Stop
Read/Write
available
1
Set up the output voltage range Bit (00): 0 ~ 10V
2
Set up the input data type
Bit (00): 0 ~ 4000
Bit (01): -2000 ~ 2000
Bit (10): 0 ~ 1000
Bit (11): 0 ~ 1000
3
Set up the output type of CH0
0: outputs the previous value
1: outputs the min. value of output range
2: outputs the mid. value of output range
3: outputs the max. value of output range
4
Set up the output type of CH1
5
Set up the output type of CH2
6
Set up the output type of CH3
11
CH0 setting error
Error code
Read
available
12
CH1 setting error
13
CH2 setting error
14
CH3 setting error
XBF-DC04A
Address
(Dec)
Description
Details
Remarks
0
Set up the run channel
Bit On(1): Run
Bit Off(0): Stop
Read/Write
available
1
Set up the output voltage range
Bit (00): 4 ~ 20mA
Bit (01): 0 ~ 20mA
2
Set up the input data type
Bit (00): 0 ~ 4000
Bit (01): -2000 ~ 2000
Bit (10): 400 ~ 2000/0 ~ 2000
Bit (11): 0 ~ 1000
3
Set up the output type of CH0
0: outputs the previous value
1: outputs the min. value of output range
2: outputs the mid. value of output range
3: outputs the max. value of output range
4
Set up the output type of CH1
5
Set up the output type of CH2
6
Set up the output type of CH3
11
CH0 setting error
Error code
Read
available
12
CH1 setting error
13
CH2 setting error
14
CH3 setting error
Summary of Contents for XGB Series
Page 70: ...XGB Analog edition manual 2 36 Program in case of IEC type ...
Page 72: ...XGB Analog edition manual 2 38 ...
Page 73: ...Chapter 2 Analog Input Module XBF AD04A 2 39 Program in case of IEC type ...
Page 491: ...XGB Analog edition manual 4 Click Yes 5 As shown below the variables are registered 13 30 ...
Page 581: ...XGB Analog edition manual 15 32 In case of IEC type APM_WRT funcion block is used ...
Page 614: ...Appendix 3 Appendix 3 4 7 Dimension of XBF AD08A Unit mm 8 Dimension of XBO AD02A Unit mm ...
Page 615: ...Appendix 3 Appendix 3 5 9 Dimension of XBO DA02A Unit mm 10 Dimension of XBO AH02A Unit mm ...
Page 616: ...Appendix 3 Appendix 3 6 11 Dimension of XBO RD01A Unit mm 12 Dimension of XBO TC02A Unit mm ...