XGB Analog edition manual
1 - 4
Items
XBF-AD04C
Number of channels
4 channels
Analog
input
Type
Voltage
Current
Range
DC 1 ~ 5V
DC 0 ~ 5V
DC 0 ~ 10V
DC -10 ~ 10V
(Input resistance: 1
㏁
min)
DC 4 ~ 20mA
DC 0 ~ 20mA
(Input resistance: 250 Ω)
Current input or Voltage input can be selected through the external
terminal wiring setting.
►In voltage mode, use V+ and COM terminal for the channel.
In current mode, short V+ and COM terminal and then use I+
and COM terminal.
Digital
output
Type
16 bit binary data (Data : 14Bit)
Range
Unsigned
value
0 ~ 16,000
Signed value
-8,000 ~ 8,000
Precise value
1,000 ~ 5,000 (1 ~ 5V)
0 ~ 5,000 (0 ~ 5V)
0 ~ 10,000 (0 ~ 10V)
-10,000 ~ 10,000 (±10V)
4,000 ~ 20,000 (4 ~ 20
㎃
)
0 ~ 20,000 (0 ~ 20
㎃
)
Percentile
value
0 ~ 10,000
Max. resolution
1/16,000
0.250
㎷
(1 ~ 5V)
0.3125
㎷
(0 ~ 5V)
0.625
㎷
(0 ~ 10V)
1.250
㎷
(±10V)
1.0
㎂
(4 ~ 20
㎃
)
1.25
㎂
(0 ~ 20
㎃
)
Accuracy
±0.2% or less (When ambient temperature 25
℃
)
±0.3% or less (When ambient temperature 0 ~ 55
℃
)
Max. conversion speed
1
㎳
/ channel
Absolute max. input
DC ±15V
DC ±30
㎃
Addition
function
Filter
Digital filter(4 ~ 64,000
㎳
)
Average
Time average (4~16,000
㎳
)
Count average (2~64,000times)
Detection alarm
Disconnection(DC 1~5V, DC 4~20
㎃
)
Hold last value
When input signal exceeds the effective range, holds the last effective
value.
Alarm function
When input signal exceeds the effective range, relevant flag turns on.
Insulation method
Photo-coupler insulation between input terminal and
PLC power (No insulation between channels)
Connection terminal
15 point terminal block
I/O points occupied
Fixed type assignment: 64
Max. attachable number
7ea (when using XBM(C)-DxxxS type)
10ea (when using XB(E)C-DxxxH type)
Consumption
current
Internal (DC 5V)
110mA
External (DC 24V)
100mA
Weight
72g
Module input power
DC 20.4~28.8V
Summary of Contents for XGB Series
Page 70: ...XGB Analog edition manual 2 36 Program in case of IEC type ...
Page 72: ...XGB Analog edition manual 2 38 ...
Page 73: ...Chapter 2 Analog Input Module XBF AD04A 2 39 Program in case of IEC type ...
Page 491: ...XGB Analog edition manual 4 Click Yes 5 As shown below the variables are registered 13 30 ...
Page 581: ...XGB Analog edition manual 15 32 In case of IEC type APM_WRT funcion block is used ...
Page 614: ...Appendix 3 Appendix 3 4 7 Dimension of XBF AD08A Unit mm 8 Dimension of XBO AD02A Unit mm ...
Page 615: ...Appendix 3 Appendix 3 5 9 Dimension of XBO DA02A Unit mm 10 Dimension of XBO AH02A Unit mm ...
Page 616: ...Appendix 3 Appendix 3 6 11 Dimension of XBO RD01A Unit mm 12 Dimension of XBO TC02A Unit mm ...