XGB Analog edition manual
(3) OUTPUT LED flikering
OUTPUT LED flikering
OUTPUT LED f
lickers 0.2s intervals
Contact nearest dealer or A/S center
No
Yes
OUTPUT LED f
lickers 1s intervals
Output channel input exceeds data
range
Enter correctly according to the output range
in the user manual
No
Yes
Parameter setting is normal
(Check with PUT command)
Operation parameter setting error
Correct the error according to user manual
(Check error code)
No
(4) Analog I/O value is abnormal.
Analog I/O value is abnormal.
External DC24V input power is OK.
Supply DC 24 power
No
Yes
PE ground is OK
Correct PE grounding according to the wiring
in the user manual
No
Yes
Parameter setting is OK
(Operation channel permit, I/O range
setting
Set up the parameters correctly according to
the user manual
No
Yes
External voltage/current selector switch
setting is correct
Set the switch according to the user manual
No
Yes
Contact nearest dealer or A/S center
6 - 48
Summary of Contents for XGB Series
Page 70: ...XGB Analog edition manual 2 36 Program in case of IEC type ...
Page 72: ...XGB Analog edition manual 2 38 ...
Page 73: ...Chapter 2 Analog Input Module XBF AD04A 2 39 Program in case of IEC type ...
Page 491: ...XGB Analog edition manual 4 Click Yes 5 As shown below the variables are registered 13 30 ...
Page 581: ...XGB Analog edition manual 15 32 In case of IEC type APM_WRT funcion block is used ...
Page 614: ...Appendix 3 Appendix 3 4 7 Dimension of XBF AD08A Unit mm 8 Dimension of XBO AD02A Unit mm ...
Page 615: ...Appendix 3 Appendix 3 5 9 Dimension of XBO DA02A Unit mm 10 Dimension of XBO AH02A Unit mm ...
Page 616: ...Appendix 3 Appendix 3 6 11 Dimension of XBO RD01A Unit mm 12 Dimension of XBO TC02A Unit mm ...