XGB Analog edition manual
4) Output status setting
(1) When the XGB basic unit is stopped, set the analog output status.
(2) When the output status setting is not specified, output the previous value.
Setting
value
-
-
-
-
-
-
-
-
Address
No. 3~ 6
-
-
-
-
-
-
Set the output status ( 2 bits)
00 : Previous value output
01 : Min value output
10 : Mid value output
11 : Max value output
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Address
Details
Setting
3
Channel 0 Output status setting
Input data type setting (bit)
00: Previous value
01: Min value
10: Mid value
11: Max value
4
Channel 1 Output status setting
5
Channel 2 Output status setting
6
Channel 3 Output status setting
5) Interpolation method setting
Show the setting of the interpolation method of each channel.
Channel 0
Address
No. 11
Interpolation method setting (2 bits per channel)
00 : Prohibition
01 : Direct interpolation
10 : S type interpolation
Channel 1
Channel 2
Channel 3
-
-
-
-
-
-
-
-
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
6) Interpolation time setting
Show the setting of interpolation time of each channel.
Channel 0
Address
No. 12
Interpolation time setting (2 bits per channel)
00 : 10[ms]
01 : 100[ms]
10 : 1[s]
11 : 60[s]
Channel 1
Channel 2
Channel 3
-
-
-
-
-
-
-
-
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
14 - 34
Summary of Contents for XGB Series
Page 70: ...XGB Analog edition manual 2 36 Program in case of IEC type ...
Page 72: ...XGB Analog edition manual 2 38 ...
Page 73: ...Chapter 2 Analog Input Module XBF AD04A 2 39 Program in case of IEC type ...
Page 491: ...XGB Analog edition manual 4 Click Yes 5 As shown below the variables are registered 13 30 ...
Page 581: ...XGB Analog edition manual 15 32 In case of IEC type APM_WRT funcion block is used ...
Page 614: ...Appendix 3 Appendix 3 4 7 Dimension of XBF AD08A Unit mm 8 Dimension of XBO AD02A Unit mm ...
Page 615: ...Appendix 3 Appendix 3 5 9 Dimension of XBO DA02A Unit mm 10 Dimension of XBO AH02A Unit mm ...
Page 616: ...Appendix 3 Appendix 3 6 11 Dimension of XBO RD01A Unit mm 12 Dimension of XBO TC02A Unit mm ...