Chapter 1 General
1 - 11
1.2.5 Analog Combo
(1) Input performance specification
Items
XBF-AH04A
No. of input channel
2 channels
Analog
input
range
Type
Voltage
Current
Range
DC 1 ~ 5V
DC 0 ~ 5V
DC 0 ~ 10V
(input resistor
: 1 MΩ or above)
DC 4 ~ 20
㎃
DC 0 ~ 20
㎃
(input resistor
250 Ω)
Input range can be set through external voltage/current selector switch after
setting at user program or I/O parameter per input channel
Digital
output
Type
12bit binary data
Range
Unsigned
value
0 ~ 4000
Signed value
-2000 ~ 2000
Precise
value
100 ~ 500 (DC 1 ~ 5V)
0 ~ 500 (DC 0 ~ 5V)
0 ~ 1000 (DC 0 ~ 10V)
400 ~ 2000 (DC 4 ~ 20
㎃
)
0 ~ 2000 (DC 0 ~ 20
㎃
)
Percentile
value
0 ~ 1000
Max. resolution
1/4000
1.25
㎷
(DC 1~5V, 0~5V)
2.5
㎷
(DC 0~10V)
5
㎂
(DC4~20
㎃
, 0~20
㎃
)
Precision
±0.5% or less
Max. conversion speed
1ms/channel
Absolute max. input
DC ±15V
DC ±25
㎃
Additional
function
Filter function
Digital filter (4 ~ 64,000
㎳
)
Averaging
function
Time averaging (4~16,000
㎳
)
Cyclic averaging (2~64,000cycle)
Moving averaging (2~100samples)
Alarm function
Disconnection detection (DC 1~5V, DC4~20
㎃
)
Summary of Contents for XGB Series
Page 70: ...XGB Analog edition manual 2 36 Program in case of IEC type ...
Page 72: ...XGB Analog edition manual 2 38 ...
Page 73: ...Chapter 2 Analog Input Module XBF AD04A 2 39 Program in case of IEC type ...
Page 491: ...XGB Analog edition manual 4 Click Yes 5 As shown below the variables are registered 13 30 ...
Page 581: ...XGB Analog edition manual 15 32 In case of IEC type APM_WRT funcion block is used ...
Page 614: ...Appendix 3 Appendix 3 4 7 Dimension of XBF AD08A Unit mm 8 Dimension of XBO AD02A Unit mm ...
Page 615: ...Appendix 3 Appendix 3 5 9 Dimension of XBO DA02A Unit mm 10 Dimension of XBO AH02A Unit mm ...
Page 616: ...Appendix 3 Appendix 3 6 11 Dimension of XBO RD01A Unit mm 12 Dimension of XBO TC02A Unit mm ...