Chapter 13 Analog Input Module (XBF-AD04C)
(8) Relationship between voltage input accuracy and wiring length
In voltage input, the wiring (cable) length between transmitter or sensor and module has an effect
on digital-converted values of the module as specified below;
Where,
Rc: Resistance value due to line resistance of cable
Rs: Internal resistance value of transmitter or sensor
Ri: Internal resistance value (1
㏁
) of voltage input module
Vin: Voltage allowed to analog input module
% Vi: Tolerance of converted value (%) due to source and cable length in voltage input
(
)
[
]
Ri
Rc
Rs
Vs
Ri
Vin
+
×
+
×
=
2
%
100
1
%
×
−
=
Vs
Vin
Vi
(1) While using a input voltage range among 1~5V, 0~5V, 0~10V, -10~10V
If the external wiring is disconnected, It will take a certain amount of time to display output data
value of 0V.If you want to reduce that time, connect the resistance about 0.1
㏁
~1
㏁
between input
channel V+ and COM.
Vs
Rs
Rc
Rc
Ri
Load
The analog input(voltage)
Vin
Remark
13 - 21
Summary of Contents for XGB Series
Page 70: ...XGB Analog edition manual 2 36 Program in case of IEC type ...
Page 72: ...XGB Analog edition manual 2 38 ...
Page 73: ...Chapter 2 Analog Input Module XBF AD04A 2 39 Program in case of IEC type ...
Page 491: ...XGB Analog edition manual 4 Click Yes 5 As shown below the variables are registered 13 30 ...
Page 581: ...XGB Analog edition manual 15 32 In case of IEC type APM_WRT funcion block is used ...
Page 614: ...Appendix 3 Appendix 3 4 7 Dimension of XBF AD08A Unit mm 8 Dimension of XBO AD02A Unit mm ...
Page 615: ...Appendix 3 Appendix 3 5 9 Dimension of XBO DA02A Unit mm 10 Dimension of XBO AH02A Unit mm ...
Page 616: ...Appendix 3 Appendix 3 6 11 Dimension of XBO RD01A Unit mm 12 Dimension of XBO TC02A Unit mm ...