XGB Analog edition manual
5.6.3 Operation parameter setting area
It describes operation parameter setting area of thermocouple input module.
Memory
address
Description
Setting value
R/W
Instruction
Hex.
Dec.
00
H
0
Designate a channel to
use
bit0:bit3, 0: stop, 1: run
R/W
PUT/GET
01
H
1
Set sensor type of CH 0
K:0, J:1, T:2, R:3
0~100
㎷
:4 (XBF-TC04B)
R/W
02
H
2
Set sensor type of CH 1
03
H
3
Set sensor type of CH 2
04
H
4
Set sensor type of CH 3
05
H
5
Designate temperature
metric system
bit0:bit3, 0: Celsius, 1:
Fahrenheit
R/W
06
H
6
Set CH 0 filter value
0 or 200 ~ 64000
R/W
07
H
7
Set CH 1 filter value
08
H
8
Set CH 2 filter value
09
H
9
Set CH 3 filter value
0A
H
10
Set averaging method
of CH 0
0: sampling
1: time average
2: count average
3: moving average
R/W
0B
H
11
Set averaging method
of CH 1
0C
H
12
Set averaging method
of CH 2
0D
H
13
Set averaging method
of CH 3
0E
H
14
Set mean value of CH 0
Time average: 400~60000 ms
Count average: 2~64000 times
Moving average: 2~100
R/W
0F
H
15
Set mean value of CH 1
10
H
16
Set mean value of CH 2
11
H
17
Set mean value of CH 3
12
H
18
Designate scaling type
bit0:bit3,
0: signed, 1: unsigned
R/W
13
H
19
Set min. value of CH 0
scaling range
Min. value
signed: -32768~[max.-1]
unsigned: 0~[max.-1]
Max. value
signed: [Min.+1]~32767
Unsigned: [Min.+1]~655535
R/W
14
H
20
Set max. value of CH 0
scaling range
15
H
21
Set min. value of CH 1
scaling range
16
H
22
Set max. value of CH 1
scaling range
17
H
23
Set min. value of CH 2
scaling range
18
H
24
Set max. value of CH 2
scaling range
19
H
25
Set min. value of CH 3
scaling range
1A
H
26
Set max. value of CH 3
5 - 42
Summary of Contents for XGB Series
Page 70: ...XGB Analog edition manual 2 36 Program in case of IEC type ...
Page 72: ...XGB Analog edition manual 2 38 ...
Page 73: ...Chapter 2 Analog Input Module XBF AD04A 2 39 Program in case of IEC type ...
Page 491: ...XGB Analog edition manual 4 Click Yes 5 As shown below the variables are registered 13 30 ...
Page 581: ...XGB Analog edition manual 15 32 In case of IEC type APM_WRT funcion block is used ...
Page 614: ...Appendix 3 Appendix 3 4 7 Dimension of XBF AD08A Unit mm 8 Dimension of XBO AD02A Unit mm ...
Page 615: ...Appendix 3 Appendix 3 5 9 Dimension of XBO DA02A Unit mm 10 Dimension of XBO AH02A Unit mm ...
Page 616: ...Appendix 3 Appendix 3 6 11 Dimension of XBO RD01A Unit mm 12 Dimension of XBO TC02A Unit mm ...