4.9 Disconnection Detection Function
(1) As a module used to measure the temperature with the RTD temperature sensor directly
connected, it detects and displays disconnection of the sensor connected. If any disconnection
occurs in the sensor used and extended lead wire, LED (ALM) will flicker in a cycle of 1 second
and produce an error code.
(2) Disconnection can be detected per channel, however, only for the channel specified to run.
LED (ALM) is used in common for all the channels. It will flicker if one or more channels are
disconnected.
(3) The figure below shows the temperature sensor’s appearance of the 3-wired RTD.
(The appearance depends on sensor type)
* A disconnection: if disconnected between terminal A and terminal board of the module in the
sensor figure.
* B disconnection: if disconnected between terminal B (two for 3-wired sensor) and terminal
board of the module in the sensor figure, or if A and B lines are all disconnected.
(4) The basic connection between RTD module and RTD Sensor is based on 3-wired RTD sensor.
If 2-wired or 4-wired sensor is used, the connection between the sensor and the module shall be
kept as 3-wired. Disconnection will be detected on the basis of 3-wired wiring.
(5) In case of disconnection, status of ALD LED and operation of disconnection flag are as follows.
- For disconnection flag, refer to 12.3.14 internal memory.
Connection status
Channel
status
ALM LED
status
Disconnection
flag
Normal
Run
Off
Off
Stop
Off
Off
A line disconnected or
B line disconnected
Run
Flicker (1s)
On
Stop
Off
Off
Any sensor is not
connected
Run
Flicker (1s)
On
Stop
Off
Off
A terminal
B terminal
B
b
A
4 - 8
Summary of Contents for XGB Series
Page 70: ...XGB Analog edition manual 2 36 Program in case of IEC type ...
Page 72: ...XGB Analog edition manual 2 38 ...
Page 73: ...Chapter 2 Analog Input Module XBF AD04A 2 39 Program in case of IEC type ...
Page 491: ...XGB Analog edition manual 4 Click Yes 5 As shown below the variables are registered 13 30 ...
Page 581: ...XGB Analog edition manual 15 32 In case of IEC type APM_WRT funcion block is used ...
Page 614: ...Appendix 3 Appendix 3 4 7 Dimension of XBF AD08A Unit mm 8 Dimension of XBO AD02A Unit mm ...
Page 615: ...Appendix 3 Appendix 3 5 9 Dimension of XBO DA02A Unit mm 10 Dimension of XBO AH02A Unit mm ...
Page 616: ...Appendix 3 Appendix 3 6 11 Dimension of XBO RD01A Unit mm 12 Dimension of XBO TC02A Unit mm ...