Chapter 9 Analog Output Option Board (XBO-DA02A)
`
(2) Sample Program(XBC Type)
(a) When the option board is in normal operation, M0000 is turned On.
U09.00.0 (Module Error) = Off
U09.00.F (Module Ready) = On
U09.01.2 (Output Channel 0 in-operation) = On
U09.01.A (Output Channel 0 Error) = Off
(b) When M0000 is ON, it turns on CH0 output state (U09.06.0) and allows output
(c) When M0000 is ON, D00100 data is moved to output CH0 Output value (U09.07) and outputs.
(3) Sample Program/(IEC Type)
(a) When the option board is in normal operation, %MX0 is turned On.
%UX0.9.0 (Module Error) = Off
%UX0.9.15 (Module Ready) = On
%UX0.9.18 (Output Channel 0 in-operation) = On
%UX0.9.26 (Output Channel 0 Error) = Off
(b) When M0000 is ON, it turns on CH0 output state (%UX0.9.96) and allows output
(c) When %MX0 is ON, CH0_Output_Value data is moved to output CH0 Output value
(%UW0.9.7) and outputs.