Chapter 13 Analog Input Module (XBF-AD04C)
13.6 Functions of Analog Input Module
Functions of XBF-AD04C conversion module are as described below.
Function
Description
Channel Run/Stop
setting
● Specify Run/Stop of the channel to execute A/D conversion.
● If the unused channel is set to Stop, whole Run time can be reduced.
Input voltage/current
range setting
● Specify analog input range to be used.
● Select range in parameter setting after select Voltage/Current switch.
● Analog input module provides two kinds of current input ranges (4~20mA,
0~20mA) and four kinds of voltage input ranges (1~5V, 0~5V, 0~10V,10~10V)
Output data format
setting
● Specify digital output type.
● 4 output data formats are provided in this module.
(Unsigned value, Signed value, Precise value, Percentile value)
A/D conversion
methods
● Sampling processing
- Sampling process will be performed if A/D conversion type is not specified.
● Filter processing
- Used to delay the sudden change of input value.
● Average processing
- Outputs average A/D conversion value based on frequency or time.
● Detection alarm
- After detecting whether disconnection of the input circuit, the alarm is
displayed by a single flag.
(Input signal range : 4 ~ 20
㎃
, 1 ~ 5 V)
● Maintenance function of valid conversion value.
- When valid conversion value is exceeded, whether conversion value
retains will be able to set.
● Alarm function
- When exceeding valid input range, alarm and maximum /minimum flag
will be generated.
13.6.1 Sampling processing
It collects analog input sign through general A/D conversion processing at a specific interval
to convert to digital. The time required for A/D conversion of analog input sign till saved on the
memory depends on the number of channels used.
(Processing time) = (Number of channels used) X (Conversion speed)
(Ex.)
If the number of channels used is 3, its process time will be
3 x 1
㎳
= 3
㎳
Sampling is to calculate the sampling value of continuous analog sign at a specific interval.
13 - 9
Summary of Contents for XGB Series
Page 70: ...XGB Analog edition manual 2 36 Program in case of IEC type ...
Page 72: ...XGB Analog edition manual 2 38 ...
Page 73: ...Chapter 2 Analog Input Module XBF AD04A 2 39 Program in case of IEC type ...
Page 491: ...XGB Analog edition manual 4 Click Yes 5 As shown below the variables are registered 13 30 ...
Page 581: ...XGB Analog edition manual 15 32 In case of IEC type APM_WRT funcion block is used ...
Page 614: ...Appendix 3 Appendix 3 4 7 Dimension of XBF AD08A Unit mm 8 Dimension of XBO AD02A Unit mm ...
Page 615: ...Appendix 3 Appendix 3 5 9 Dimension of XBO DA02A Unit mm 10 Dimension of XBO AH02A Unit mm ...
Page 616: ...Appendix 3 Appendix 3 6 11 Dimension of XBO RD01A Unit mm 12 Dimension of XBO TC02A Unit mm ...