XGB Analog edition manual
12.13.2 Program example using PUT/GET instruction
(1) Program example (XBC Type)
(a) It writes h0001 at address 0 of slot 1 in order to enable CH0 by using PUT instruction.
(b) If module is under normal operation, M0000 is on.
U0A.00.F(Module Ready) = On
U0A.00.E(Module H/W error) = Off
U0A.01.0(CH 0 running) = On
(c) If M0000 is on, temp. conversion value of CH0 moves to D0000.
Current temp. conversion value, 278(27.8
℃
2) is saving in U0A.04.
(d) If disconnection error occurs at CH0, U0A.01.4 (CH0 disconnection) is on and M0001 bit is set.
(e) If M0000 is on, setting error (address 16) of CH0 moves to D0001. Since setting error (address
16) of CH0 is 0, there is no setting error.
12 - 32