Chapter 4 RTD Input Module (XBF-RD04A, XBF-RD01A)
4.11 Filtering Function
Based on the filter value (time-constant) which defines the temperature-converted value of the specified
channel, it performs and outputs calculation as below.
)
40
(
(
used
Channels
value
Filter
used)
Channels
temp.x40
input
(Presently
)
value
Filter
temp.x
filtered
Previously
e
temperatur
Filtered
×
+
×
+
=
ms
ms
ms
ms
• Filtering constant setting range = 160 ~ 64000 [ms]
Temperature(
℃
Filtered Temperature
Actual temperature
100
℃
63.2
℃
0
℃
Time (ms)
Filtering
Constant
(ms)
4 - 11